Adapter Parameters

20-COMM-R Remote I/O Adapter User Manual

Publication 20COMM-UM004D-EN-P

09

[Reset Module]
No action if set to ‘0’ (Ready). Resets the adapter if

set to ‘1’ (Reset Module). Restores the adapter to

its factory default settings if set to ‘2’ (Set Defaults).

This parameter is a command. It will be reset to ‘0’

(Ready) after the command has been performed.

Default:

0 = Ready

Values:

0 = Ready

1 = Reset Module

2 = Set Defaults

Type:

Read/Write

Reset Required: No

10

[Comm Flt Action]
Sets the action that the adapter and drive will take

if the adapter detects that I/O communication has

been disrupted. This setting is effective only if I/O

that controls the drive is transmitted through the

adapter. When communication is re-established,

the drive will automatically receive commands over

the network again.

Default:

0 = Fault

Values:

0 = Fault

1 = Stop

2 = Zero Data

3 = Hold Last

4 = Send Flt Cfg

Type:

Read/Write

Reset Required: No

11

[Idle Flt Action]
Sets the action that the adapter and drive will take

if the adapter detects that the controller is in

program mode or faulted. This setting is effective

only if I/O that controls the drive is transmitted

through the adapter. When the controller is put

back in Run mode, the drive will automatically

receive commands over the network again.

Default:

0 = Fault

Values:

0 = Fault

1 = Stop

2 = Zero Data

3 = Hold Last

4 = Send Flt Cfg

Type:

Read/Write

Reset Required: No

Parameter
No. Name and Description

Details

!

ATTENTION: Risk of injury or equipment damage exists. If the adapter is

transmitting I/O that controls the drive, the drive may fault when you reset the

adapter. Determine how your drive will respond before resetting a connected

adapter.

!

ATTENTION: Risk of injury or equipment damage exists. Parameter 10 -

[Comm Flt Action] lets you determine the action of the adapter and connected

drive if I/O communication is disrupted. By default, this parameter faults the

drive. You can set this parameter so that the drive continues to run, however,

precautions should be taken to verify that the setting of this parameter does not

create a risk of injury or equipment damage. When commissioning the drive,

verify that your system responds correctly to various situations (for example, a

disconnected cable).

!

ATTENTION: Risk of injury or equipment damage exists. Parameter 11 - [Idle

Flt Action] lets you determine the action of the adapter and connected drive

when the controller is idle. By default, this parameter faults the drive. You can

set this parameter so that the drive continues to run, however, precautions

should be taken to verify that the setting of this parameter does not create a risk

of injury or equipment damage. When commissioning the drive, verify that your

system responds correctly to various situations (for example, a faulted

controller).