Connecting the adapter to the drive, Connecting the adapter to the drive -4 – Rockwell Automation 20-COMM-R Remote I/O Adapter User Manual
Page 20

2-4
Installing the Adapter
20-COMM-R Remote I/O Adapter User Manual
Publication 20COMM-UM004D-EN-P
The settings for all of the Configuration DIP Switches can be verified by
viewing Diagnostic Item number 28 (
Connecting the Adapter to
the Drive
1. Remove power from the drive.
2. Use static control precautions.
3. Remove or open the drive cover.
4. Connect the Internal Interface cable to the DPI port on the drive and
then to the DPI connector on the adapter (see
Figure 2.3
).
5. Secure and ground the adapter to the drive (see
) by doing the
following:
– On a PowerFlex 70 drive, fold the Internal Interface cable behind the
adapter and mount the adapter on the drive using the four captive
screws.
– On a PowerFlex 700, PowerFlex 700H, or PowerFlex 700S drive,
mount the adapter on the drive using the four captive screws.
Important: Tighten all screws to properly ground the adapter.
Recommended torque is 0.9 N•m (8.0 lb•in).
!
ATTENTION: Risk of injury or death exists. The PowerFlex
drive may contain high voltages that can cause injury or death.
Remove power from the drive, and then verify power has been
discharged before installing or removing the adapter.