Table 6.B Adapter Events

Code

Event

Description

1

No Event

Empty event queue entry.

2

DPI Bus Off Flt

A bus-off condition was detected on DPI. This event may be caused by loose or broken cables or by noise.

3

Ping Time Flt

A ping message was not received on DPI within the specified time.

4

Port ID Flt

The adapter is not connected to a correct port on a DPI product.

5

Port Change Flt

The DPI port changed after start up.

6

Host Sent Reset

The drive sent a reset event message.

7

EEPROM Sum Flt

The EEPROM in the adapter is corrupt.

8

Online @ 125kbps

The adapter detected that the drive is communicating at 125 kbps.

9

Online @ 500kbps

The adapter detected that the drive is communicating at 500 kbps.

10

Bad Host Flt

The adapter was connected to an incompatible product.

11

Dup Port Flt

Another peripheral with the same port number is already in use.

12

Type 0 Login

The adapter has logged in for Type 0 control.

13

Type 0 Time Flt

The adapter has not received a Type 0 status message within the specified time.

14

DL Login

The adapter has logged into a Datalink.

15

DL Reject Flt

The drive rejected an attempt to log in to a Datalink because the Datalink is not supported or is used by

another peripheral.

16

DL Time Flt

The adapter has not received a Datalink message within the specified time.

17

Control Disabled

The adapter has sent a ‘Soft Control Disable’ command to the drive.

18

Control Enabled

The adapter has sent a ‘Soft Control Enable’ command to the drive.

19

Reserved

20

Normal Startup

The adapter successfully started up.

21

Message Timeout

A Client-Server message sent by the adapter was not completed within 1 sec.

22

DPI Fault Msg

The DPI Host drive has faulted.

23-27

Reserved

28

DPI Fault Clear

The drive issued this because a fault was cleared.

29

Reserved

30

NET Comm Flt

The adapter detected a communications fault on the network.

31

NET Sent Reset

The controller issued a reset command to the adapter.

32

NET Idle Flt

The adapter detected an ‘idle’ condition on the network.

33

NET Timeout Flt

The adapter detected a timeout on the network.

34

Flt Cfg Error

One of the Flt Cfg xx parameters is set to a value greater than 65535 and the drive requires a 16-bit value.

35

Reserved

36

Manual Reset

The adapter was reset by changing its Reset Module parameter.

37

Language CRC Bad

The language text memory segment is corrupt.

Advertising