Adapter Parameters

B-3

20-COMM-R Remote I/O Adapter User Manual

Publication 20COMM-UM004D-EN-P

12

[DPI I/O Config]
Sets the I/O that is transferred through the adapter.

Default:

xxx0 0001

Bit Values:

0 = I/O Disabled

1 = I/O Enabled

Type:

Read/Write

Reset Required: Yes

13

[DPI I/O Active]
Displays the I/O that the adapter is actively

transmitting. The value of this parameter will

usually be equal to the value of

Parameter 12 -

[DPI I/O Config] unless the parameter was

changed and the adapter was not reset.

Bit Values:

0 = I/O Disabled

1 = I/O Enabled

Type:

Read Only

14

[Flt Cfg Logic]
Sets the Logic Command data that is sent to the

drive if any of the following is true:
Parameter 10 - [Comm Flt Action] is set to ‘4’

(Send Flt Cfg) and I/O communication is

disrupted.

Parameter 11 - [Idle Flt Action] is set to ‘4’

(Send Flt Cfg) and the controller is idle.

The bit definitions will depend on the product to

which the adapter is connected. See

Appendix D

or the documentation for the drive being used.

Default:

0000 0000 0000 0000

Minimum:

0000 0000 0000 0000

Maximum:

1111 1111 1111 1111

Type:

Read/Write

Reset Required: No

15

[Flt Cfg Ref]
Sets the Reference data that is sent to the drive if

any of the following is true:
Parameter 10 - [Comm Flt Action] is set to ‘4’

(Send Flt Cfg) and I/O communication is

disrupted.

Parameter 11 - [Idle Flt Action] is set to ‘4’

(Send Flt Cfg) and the controller is idle.

Adapter

Parameter 7 - [Ref/Fdbk Size] displays

the size of the Reference (16-bit or 32-bit) in the

drive.

Default:

0

Minimum:

0

Maximum:

4294967295

Type:

Read/Write

Reset Required: No

Important: If the drive uses a 16-bit

Reference, the most significant word of

this value must be set to zero (0) or a

fault will occur.

Parameter
No. Name and Description

Details

Bit

Definition

Not

Used

Not

Used

Not

Used

Dat

alink

D

Dat

alink

C

Dat

alink

B

Dat

alink

A

Cmd/

Ref

Default

x

x

x

0

0

0

0

1

Bit

7

6

5

4

3

2

1

0

Bit

Definition

Not

Used

Not

Used

Not

Used

Dat

alink

D

Dat

alink

C

Dat

alink

B

Dat

alink

A

Cmd

/Ref

Default

x

x

x

0

0

0

0

1

Bit

7

6

5

4

3

2

1

0