Rockwell Automation 20-COMM-R Remote I/O Adapter User Manual

Page 54

Advertising
background image

4-18

Using Discrete and Block Transfer I/O

20-COMM-R Remote I/O Adapter User Manual

Publication 20COMM-UM004D-EN-P

Block Transfer Write Example

The following data is used for this example.

• Rack 1

• Group 4 (upper half rack)

• Slot 0 (always 0)

• Control Block N10:0 (user defined)

• Data File N22:0 (user defined)

• Buffer File M0:x.200 (Block Transfer Writes always start with M0,

where x is the slot in which the 1747-SN scanner card is in. In this
example, the 1747-SN card is in slot 2.)

• Requested Word Count is 18 or less (see

See Figure 4.1 on page 4-2

or

See Figure 4.2 on page 4-3

)

• Transmitter Word Count (always 0)

• Control Block Length (always 3)

Important: Each Block Transfer needs to be offset by 100 (M0:x.200) and

the default is 3300 words, so you can perform up to 33 Block
Transfers. See the advanced configuration for your 1747-SN
scanner card under channel configuration.

Figure 4.12 SLC 500 Series C, FRN 3.xx and Higher, Example Ladder Logic for

Block Transfer Write

Advertising