Setting the configuration dip switches – Rockwell Automation 20-COMM-R Remote I/O Adapter User Manual

Page 19

Advertising
background image

Installing the Adapter

2-3

20-COMM-R Remote I/O Adapter User Manual

Publication 20COMM-UM004D-EN-P

The Rack Address Rotary Switch settings can be verified (as a decimal
value) by viewing Diagnostic Device Item number 29 (

page 6-4

).

Setting the Configuration DIP Switches

Set the Configuration DIP Switches (

Figure 2.2

) to match your application

specifics for the controller and network.

Figure 2.2 Setting the Configuration DIP Switches

The Configuration DIP Switches SW7 and SW8 settings can be verified by
viewing Parameter 24 - [Switches] with any of the following drive
configuration tools:

• PowerFlex HIM

• Connected Components Workbench software, version 1.02 or later

• Drive Explorer software, version 2.01 or later

• DriveExecutive software, version 3.01 or later

Switches

Setting Description

SW1 and SW2

1

2 SW1 and SW2 are used together to set the starting module group:

0

0 Group 0 (Default)

1

0 Group 2

0

1 Group 4

1

1 Group 6 – Only used if SW4 is set to “0” (1/4 rack).

SW3

0

Not the last RIO rack (Default)

1

Last RIO group within the rack

SW4

0

1/4 rack (Default)

1

1/2 rack

SW5

0

Not Used

SW6

0

Not Used

SW7 and SW8

7

8 SW7 and SW8 are used together to set the Remote I/O baud rate:

0

0 57.6 kbps (Default)

1

0 115.2 kbps

0

1 230.4 kbps

1

1 Disables all hardware switches. Instead, the adapter uses the values

of the following parameters:
Parameter 3 - [RIO Addr Cfg] for the rack address

Parameter 5 - [RIO Rate Cfg] for the baud rate

Parameter 25 - [Start RIO Group] for the starting module group

Parameter 26 - [Last RIO Rack] for the last physical rack

Parameter 27 - [Rack Size] for the rack size

ON

1 2 3 4 5 6 7 8

On = 1

Off = 0