Rockwell Automation 20-COMM-R Remote I/O Adapter User Manual

Page 86

Advertising
background image

B-4

Adapter Parameters

20-COMM-R Remote I/O Adapter User Manual

Publication 20COMM-UM004D-EN-P

16

17

18

19

20

21

22

23

[Flt Cfg A1 In]

[Flt Cfg A2 In]

[Flt Cfg B1 In]

[Flt Cfg B2 In]

[Flt Cfg C1 In]

[Flt Cfg C2 In]

[Flt Cfg D1 In]

[Flt Cfg D2 In]
Sets the data that is sent to the Datalink in the

drive if any of the following is true:
Parameter 10 - [Comm Flt Action] is set to ‘4’

(Send Flt Cfg) and I/O communication is

disrupted.

Parameter 11 - [Idle Flt Action] is set to ‘4’

(Send Flt Cfg) and the controller is idle.

Adapter

Parameter 8 - [Datalink Size] displays

the size of the Datalinks (16-bit or 32-bit) in the

drive.

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Minimum:

0

Maximum:

4294967295

Type:

Read/Write

Reset Required: No

Important: If the drive uses 16-bit

Datalinks, the most significant word of

this value must be set to zero (0) or a

fault will occur.

24

[Switches]
Displays the status of the adapter Configuration

DIP Switches. By default, these switches are

‘enabled’, and the adapter is configured based on

their settings. If SW7 and SW8 are both set to ‘On’,

all hardware switches are ‘disabled’ and the

adapter is configured using values in the following

adapter parameters:
Parameter 3 - [RIO Addr Cfg]

Parameter 5 - [RIO Rate Cfg]

Parameter 25 - [Start RIO Group]

Parameter 26 - [Last RIO Rack]

Parameter 27 - [Rack Size]

Bit Values:

0 = Disabled

1 = Enabled

Type:

Read Only

25

[Start RIO Group]
Sets the Remote I/O starting module group if the

hardware switches have been disabled. All

hardware switches are disabled by setting

Configuration DIP Switches SW7 and SW8 both to

‘On’.

Default:

0 = Group 0

Values:

0 = Group 0

1 = Group 2

2 = Group 4

3 = Group 6 (allowed

for 1/4 rack only)

Type:

Read/Write

Reset Required: Yes

26

[Last RIO Rack]
Sets the last (or not last) physical group within a

rack address on a Remote I/O network if the

hardware switches have been disabled. All

hardware switches are disabled by setting

Configuration DIP Switches SW7 and SW8 both to

‘On’. Set this parameter to ‘1’ (Enabled) to indicate

that a drive is the last rack.

Default:

0 = Disabled

Bit Values:

0 = Disabled

1 = Enabled

Type:

Read/Write

Reset Required: Yes

27

[Rack Size]
Sets the rack size if the hardware switches have

been disabled. All hardware switches are disabled

by setting Configuration DIP Switches SW7 and

SW8 both to ‘On’.

Default:

0 = 1/4 rack

Bit Values:

0 = 1/4 rack

1 = 1/2 rack

Type:

Read/Write

Reset Required: Yes

Parameter
No. Name and Description

Details