Powerflex 750-series drives, Logic command word – Rockwell Automation 20-COMM-R Remote I/O Adapter User Manual

Page 111

Advertising
background image

Logic Command/Status Words

D-5

20-COMM-R Remote I/O Adapter User Manual

Publication 20COMM-UM004D-EN-P

PowerFlex 750-Series Drives

Important: When using a 20-COMM-R adapter with a PowerFlex

750-Series drive, the upper word (bits 16…31) of the Logic
Command and Logic Status words are not accessible and
cannot be used.

Logic Command Word

Logic Bits

31…15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Command

Description

x Normal Stop

0 = Not Normal Stop

1 = Normal Stop

x

Start

(1)

0 = Not Start

1 = Start

x

Jog 1

(2)

0 = Not Jog 1 (Par. 556)

1 = Jog 1

x

Clear Fault

(3)

0 = Not Clear Fault

1 = Clear Fault

x

x

Unipolar

Direction

00 = No Command

01 = Forward Command

10 = Reverse Command

11 = Hold Direction Control

x

Manual

0 = Not Manual

1 = Manual

x

Reserved

x

x

Accel Time

00 = No Command

01 = Use Accel Time 1 (Par. 535)

10 = Use Accel Time 2 (Par. 536)

11 = Use Present Time

x

x

Decel Time

00 = No Command

01 = Use Decel Time 1 (Par. 537)

10 = Use Decel Time 2 (Par. 538)

11 = Use Present Time

x

Ref Select 1

000 = No Command

001 = Ref A Select (Par. 545)

010 = Ref B Select (Par. 550)

011 = Preset 3 (Par. 573)

100 = Preset 4 (Par. 574)

101 = Preset 5 (Par. 575)

110 = Preset 6 (Par. 576)

111 = Preset 7 (Par. 577)

x

Ref Select 2

x

Ref Select 3

x

Reserved

(1)

A Not Stop condition (logic bit 0 = 0) must first be present before a 1 = Start condition will start the drive.

(2)

A Not Stop condition (logic bit 0 = 0) must first be present before a 1 = Jog 1/Jog 2 condition will jog the drive. A transition to a ‘0’ will stop

the drive.

(3)

To perform this command, the value must switch from ‘0’ to ‘1’.