This chapter provides instructions for installing the adapter in a PowerFlex
7-Class drive.

Preparing for an Installation

Before installing the adapter, verify that you have all required equipment.
See

Required Equipment on page 1-3

.

Selecting Remote I/O Cables

Remote I/O adapters are connected to the Remote I/O network or link with
twinaxial cable used for Remote I/O and Data Highway Plus (DH+)
communications. When selecting a cable, remember these points:

• Only 1770-CD Belden #9463 is tested and approved for Remote I/O and

DH+ installations. Use other cables at your own risk.

• The maximum cable length depends on the baud rate.

• All three connectors (blue, shield, and clear) must be connected at each

node.

• Do not use a star topology. Only two cables may be connected at any

wiring point. You can use a series topology and daisy-chain two wires at
a point.

Topic

Page

Preparing for an Installation

2-1

Selecting Remote I/O Cables

2-1

Commissioning the Adapter

2-2

Connecting the Adapter to the Drive

2-4

Connecting the Adapter to the Network

2-7

Applying Power

2-8

Baud Rate

Maximum Cable Length

57.6 Kbps

3,048 m (10,000 ft)

115.2 Kbps

1,524 m (5,000 ft)

230.4 Kbps

762 m (2,500 ft)