Appendix b, Adapter parameters, Parameter list – Rockwell Automation 20-COMM-R Remote I/O Adapter User Manual

Page 83: Badapter parameters, Appendix

Advertising
background image

20-COMM-R Remote I/O Adapter User Manual

Publication 20COMM-UM004D-EN-P

Appendix

B

Adapter Parameters

This appendix provides information about the adapter parameters. For
configuration tools to monitor or change parameter values of the drive,
adapter, and other connected peripherals, see

Configuration Tools on

page 3-1

.

Parameter List

Parameter
No. Name and Description

Details

01

[DPI Port]
Displays the port to which the adapter is

connected. This will usually be port 5.

Minimum:

0

Maximum:

7

Type:

Read Only

02

[DPI Data Rate]
Displays the data rate used by the drive. This data

rate is set in the drive and the adapter detects it.

Values:

0 = 125 Kbps

1 = 500 Kbps

Type:

Read Only

03

[RIO Addr Cfg]
Sets the Remote I/O rack address (displayed as a

decimal value) used by the adapter if the hardware

switches have been disabled. All hardware

switches are disabled by setting Configuration DIP

Switches SW7 and SW8 both to ‘On’. (Updates

Parameter 04 - [RIO Addr Actual] after reset).

Default:

1

Minimum:

0

Maximum:

63 decimal

Type:

Read/Write

Reset Required: Yes

04

[RIO Addr Actual]
Displays the Remote I/O rack address (as a

decimal value) actually used by the adapter.

Minimum:

0

Maximum:

63 decimal

Type:

Read Only

05

[RIO Rate Cfg]
Sets the network baud rate at which the adapter

communicates if the hardware switches have been

disabled. All hardware switches are disabled by

setting Configuration DIP Switches SW7 and SW8

both to ‘On’. (Updates

Parameter 06 - [RIO Rate

Act] after a reset.)

Default:

0 = 57.6 Kbps

Values:

0 = 57.6 Kbps

1 = 115.2 Kbps

2 = 230.4 Kbps

Type:

Read/Write

Reset Required: Yes

06

[RIO Rate Actual]
Displays the actual network baud rate used by the

adapter.

Values:

0 = 57.6 Kbps

1 = 115.2 Kbps

2 = 230.4 Kbps

Type:

Read Only

07

[Ref/Fdbk Size]
Displays the size of the Reference/Feedback. The

drive determines the size of the Reference/

Feedback.

Values:

0 = 16-bit

1 = 32-bit

Type:

Read Only

08

[Datalink Size]
Displays the size of each Datalink word. The drive

determines the size of Datalinks.

Values:

0 = 16-bit

1 = 32-bit

Type:

Read Only

Advertising