5-10

Using Block Transfer Messaging

20-COMM-R Remote I/O Adapter User Manual

Publication 20COMM-UM004D-EN-P

Ladder Logic Program

Figure 5.4 PLC-5 Example Ladder Logic for Block Transfer Messaging

The word length used in the BTW and BTR must be equal to 20, 30, or 60.
It must also be greater than or equal to the byte length used in Word 0 of the
message, converted to words (1 word = 2 bytes).

The user initiates a messaging transaction by setting the User Execute Message Input bit true. This causes one messaging BTW to be sent to the 20-COMM-R.

0000

N7:2

0

User

EXECUTE MESSAGE

Input

ONS

B3:0

1

L

B3:0

0

Execute Message

This rung causes one messaging BTW to execute when the 20-COMM-R is ready to receive a Messaging BTW and the user has requested the BTW.

0001

B3:0

0

Execute Message

I:010

11

Messaging BT
BTW AVAILABLE

Status

I:010

12

Messaging BT
BTR AVAILABLE

Status

EN

DN

ER

BTW

Block Transfer Write

Module Type Generic Block Transfer

Rack

001

Group

0

Module

0

Control Block

BT9:2

Data File

N12:0

Length

20

Continuous

No

BTW

U

B3:0

0

Execute Message

This rung will wait until a BTR is available from the 20-COMM-R module and then execute a BTR.

0002

I:010

12

Messaging BT
BTR AVAILABLE

Status

EN

DN

ER

BTR

Block Transfer Read

Module Type Generic Block Transfer

Rack

001

Group

0

Module

0

Control Block

BT9:3

Data File

N13:0

Length

20

Continuous

No

BTR

0003

END