Using Block Transfer Messaging

5-7

20-COMM-R Remote Adapter I/O User Manual

Publication 20COMM-UM004D-EN-P

ControlLogix Controller

Example

Data Format for a Read and Write Parameter

The data in this example is for a PowerFlex 70 drive at Remote I/O rack.

The following set of arrays shows a read of drive parameter 1 - [Output
Freq]. The value of parameter 1 is 213 (21.3 Hz).

MsgBlockTransferWrite (Request Data) to Read Drive Parameter 1 (Hex)

MsgBlockTransferRead (Response Data) to Read Drive Parameter 1 (Hex)

The following set of data files shows a write of drive parameter 41 [Motor
NP Volts]. The value written is 2300 (230.0V AC).

MsgBlockTransferWrite (Request Data) to Write to Drive Parameter 41 (Hex)

MsgBlockTransferRead (Response Data) to Write to Drive Parameter 41 (Hex)

See

Formatting Block Transfer Messages on page 5-2

for more information

on block transfer messages.

Int Address

Value (hex) Description

See Page

Offset 0

000A

Length of Message = 10 bytes (A hex)

5-3

Offset 1

0081

Required Setting

5-3

Offset 2

000E

Service = Get_Attribute_Single

C-1

Offset 3

0093

Class = 93 DPI Parameter Object

C-5

Offset 4

0001

Instance = Parameter 1 (1 hex)

C-5

Offset 5

0009

Attribute = 09 DPI Parameter Value

C-6

Int Address Value (hex)

Description

See Page

Offset 0

0004

Length of Message = 4 bytes

5-4

Offset 1

0000

The Message was Successful

5-4

Offset 2

0000

Offset 3

00D5

Response Data = 213 (D5 hex) = 21.3 Hz.

n/a

Int Address Value (hex)

Description

See Page

Offset 0

000C

Length of Message = 12 bytes (C hex)

5-3

Offset 1

0081

Required Setting

5-3

Offset 2

0010

Service = Set_Attribute_Single

C-1

Offset 3

0093

Class = 93 DPI Parameter Object

C-5

Offset 4

0029

Instance = Parameter 41 (29 hex)

C-5

Offset 5

0009

Attribute = 09 DPI Parameter Value

C-6

Offset 6

08FC

Data = 2300 (8FC hex) = 230.0V AC

n/a

Int Address Value (hex)

Description

See Page

Offset 0

0002

Length of Message = 2 bytes

5-4

Offset 1

0000

The Message was Successful

5-4

Offset 2

0000