Setting the node address, Setting the data rate, R to – Rockwell Automation 20-COMM-K CANopen Adapter User Manual

Page 29: Setting the data rate on

Advertising
background image

Configuring the Adapter

3-3

20-COMM-K CANopen Adapter User Manual

Publication 20COMM-UM012B-EN-P

Setting the Node Address

The node address is normally set by the adapter Node Address switches
(

Figure 2.1

), and is unique to each node on the network. If both switches are

set to “0,” the value of Parameter 03 - [COPN Addr Cfg] determines the
node address.

1. Set the value of Parameter 03 - [COPN Addr Cfg] to a unique node

address.

Figure 3.1

Example COPN Node Addr Cfg LCD HIM Screen

2. Reset the adapter (see

Resetting the Adapter on page 3-9

).

Setting the Data Rate

The data rate is normally set by the adapter Data Rate switch (

Figure 2.2

),

and must be the same for each node on the network. If the Data Rate switch
is set to “PGM” (Program), the value of Parameter 05 - [COPN Rate Cfg]
determines the data rate. Your application may require a different setting.

1. Set the value of Parameter 05 - [COPN Rate Cfg] to the data rate at

which your network is operating.

Figure 3.2

Example COPN Rate Cfg LCD HIM Screen

2. Reset the adapter (see

Resetting the Adapter on page 3-9

).

Port 5 Device

20-COMM-K

Parameter #: 03
COPN Addr Cfg

01

1 <> 127

Default = 1

Value

Data Rate

0

10 Kbps

1

20 Kbps

2

50 Kbps

3

125 Kbps

4

250 Kbps

5

500 Kbps (default)

6

1000 Kbps

Port 5 Device

20-COMM-K

Parameter #: 05
COPN Rate Cfg

5

500K

Advertising