Table C.A

describes the objects for the communication profile and

Table C.B

describes the manufacturer specific objects.

Table C.A Communication Profile Area

Topic

Page

CANopen Object Tables

C-1

Emergency Object

C-4

Index

Sub Index

Type

Access

Name and Description

0x1000

0

U32

Read

Device Type.
Describes the type of device.

0x1001

0

U8

Error register Bit 0.
Indicates that a generic error has occurred.

0x1003

0

U8

Read/Write

Number of errors.
Writing a 0 to this sub index clears the list.
The error list starts at sub index 1.

1…5

U32

Read

Pre-defined error field.
A list of errors that have occurred.
Sub index 1 contains the most recent error.

0x1005

0

U32

Read/Write

COB-ID Sync.
This is the ID for the sync message.

0x1008

0

Visible
string

Read

Manufacturer device name
(Family text from DPI Device object)

0x100A

0

Visible
string

Read

Manufacturer software version (Product revision from
DPI Device object as “SW V.MAJOR.MINOR” string)

0x100C

0

U16

Read/Write

Guard time
This parameter is used together with Life time factor
for the Life guarding protocol. The NMT master
guards the node at this period in milliseconds.

0x100D

0

U8

Read/Write

Life time factor.
If the node has not been guarded in the time period
Life-time factor x Guard time, a “Guard Error” event is
logged and a remote node error is indicated through
the “Life Guarding event” service.

0x1014

0

U32

Read/Write

COB-ID EMCY.
This is the ID for the Emergency object

0x1400…
0x1404

0

U8

Read

Receive PDO parameter.
Number of entries (= 2)

1

U32

Read/Write

COB ID used by PDO

2

U8

Read/Write

Transmission type

0x1600…
0x1604

0

U8

Read/Write

Receive PDO mapping.
Number of mapped application objects (N)

1…N

U32

Read/Write

Mapped object #N