Rockwell Automation 20-COMM-K CANopen Adapter User Manual

Page 32

Advertising
background image

3-6

Configuring the Adapter

20-COMM-K CANopen Adapter User Manual
Publication 20COMM-UM012B-EN-P

4. Set Parameter 25 - [COS Status Mask] for the bits in the Logic Status

word that should be checked for changes. The bit definitions for the
Status Mask will depend on the drive to which the adapter is connected.
Refer to

Appendix D

or the drive documentation.

Figure 3.6

Example COS Status Mask LCD HIM Screen

5. Set Parameter 26 - [COS Fdbk Change] for the amount of change to

the Feedback that is required to trigger a Change of State message.

Figure 3.7

Example COS Fdbk Change LCD HIM Screen

Using Cyclic Data Exchange

With cyclic data exchange, a PDO is sent periodically.

1. With the CANopen configuration tool, set the transmission mode of the

TPDO1 (Transmit PDO) of the adapter to “0” (synchronous) or “254”
(asynchronous).

2. Set Parameter 24 - [PDO1 Trigger] to “1” (Cyclic).

Figure 3.8

Example DPO1 Trigger LCD HIM Screen

3. Set Parameter 27 - [Cyclic Interval] for the desired time interval

between two transmissions.

Figure 3.9

Example Cyclic Interval LCD HIM Screen

Value Description
0

Ignore this logic bit. (Default)

1

Use this logic bit.

Port 5 Device

20-COMM-K

Parameter #: 25
COS Status Mask
x x x x x x x x x x x 0 0 0 0

1

Bit 0

b00

Default = 1

Port 5 Device

20-COMM-K

Parameter #: 26
COS Fdbk Change

1

1 <> 4294967295

Port 5 Device

20-COMM-K

Parameter #: 24
PDO1 Trigger

1

Cyclic

Value Trigger
0

COS (Default)

1

Cyclic

Port 5 Device

20-COMM-K

Parameter #: 27
Cyc Interval

0.02

s

0.02 <> 655.35

Default = 0.02 s