Transmit pdo mapping, Transmit pdo mapping -9 – Rockwell Automation 20-COMM-K CANopen Adapter User Manual

Page 51

Advertising
background image

Using I/O Messaging

5-9

20-COMM-K CANopen Adapter User Manual

Publication 20COMM-UM012B-EN-P

Regardless of the Datalink combination, Datalink x1 Out will always
contain the LSW and Datalink x2 Out will always contain the MSW. In the
following example, the PowerFlex 70 drive Parameter 242 - [Power Up
Marker] contains a value of 88.4541 hours.

Conversion Example:

Parameter 242 - [Power Up Marker] = 88.4541 hours
MSW = 000D

hex

= 1101

binary

= 2

19

+ 2

18

+ 2

16

= 851968

LSW = 7F3D

hex

= 32573

Engineering Value = 851968 + 32573 = 884541
Parameter 242 Displayed Value = 88.4541 Hrs

Transmit PDO Mapping

The Transmit PDOs have a default mapping as shown in

Table 5.F

. The

mapping can be changed if desired. Since every PDO can contain up to
eight bytes of data, it is possible to map, for example, Datalink A1, A2, C1,
and C2 to the same PDO number when using a drive with 16-bit Datalinks.

Table 5.F Default TPDO Mapping

Important: For a 32-bit drive, PDO mapping must be changed from their

default values.

Datalink

Word

Parameter

Data (Hex)

A2 Out

MSW

242

000D

B1 Out

LSW

242

7F3D

TPDO#

Default Mapping

Enabled

Remap

Initial Transmission Type

(1)

(1)

Table 5.H

shows the transmission types for the PDO.

1

Product Logic Status (0x2201)
+Feedback 16-bit (0x2204)

Yes

No

254 (Asynchronous, COS)

2

Datalink A1 Out 16-bit (0x2216)
+Datalink A2 Out 16-bit (0x2218)

No

Yes

253 (Asynchronous, RTR)

3

Datalink B1 Out 16-bit (0x221A)
+Datalink B2 Out 16-bit (0x221C)

No

Yes

253 (Asynchronous, RTR)

4

Datalink C1 Out 16-bit (0x221E)
+Datalink C2 Out 16-bit (0x2220)

No

Yes

253 (Asynchronous, RTR)

5

Datalink D1 Out 16-bit (0x2222)
+Datalink D2 Out 16-bit (0x2224)

No

Yes

253 (Asynchronous, RTR)

TIP: If a 32-bit drive parameter is mapped to a Datalink pair, it is not
recommended to map part of the pair (that is, A1 or A2) to two different
PDOs since this can give data inconsistency.