Rockwell Automation 20-COMM-K CANopen Adapter User Manual

Page 94

Advertising
background image

E-18

CANopen Network Example

20-COMM-K CANopen Adapter User Manual
Publication 20COMM-UM012B-EN-P

5. On the Process Data Objects tab, set the Transmission Type of the

RPDOs to asynchronous (Manuf. Event). For RPDOs, only the
transmission mode (synchronous or asynchronous) is relevant.

Leave the Transmission Type of all TPDOs set to asynchronous
(Profile Event)
, so the PDOs are sent when one of its variables has
changed in the PLC program.

6. On the Predefined Objects tab, check the Device generates SYNC

message box (sub-tab Synchronisation Message). Note that the
Communication Cycle Period can be changed on this tab.