Start at power up, Stop modes, Start at power up stop modes – Rockwell Automation 20C PowerFlex 700H Drives Programming User Manual

Page 101: For impor

Advertising
background image

Rockwell Automation Publication 20C-PM001F-EN-P - March 2012

101

Application Notes

Appendix B

Start At Power Up

A powerup delay time of up to 30 seconds can be programmed through [Powerup
Delay], parameter 167. After the time expires, the drive will start if all of the start
permissive conditions are met. Before that time, restart is not possible.

Stop Modes

[Powerup Delay]

Time Expired?

Start At PowerUp

Yes

Powerup Terminated!

Normal Mode

No

No

No

Powerup Start

Is the terminal block Run,

Run Forward or Run Reverse

Input Closed?

Yes

Yes

All Start Permissives Met?

1. No fault conditions present.

2. No Type 2 alarm conditions present.

3. The terminal block programmed

enable input is closed.

4. The Stop input (from all sources) is

received.

Mode

Description

Coast

This method releases the motor and allows the load to stop by friction.
1. On Stop, the drive output goes immediately to zero (off).
2. No further power is supplied to the motor. The drive has released control.
3. The motor will coast for a time that is dependent on the mechanics of the system (inertia, friction, etc).
Important: When a “Coast” stop is performed, the drive requires that the motor flux be completely
dissipated before a re-start command will take affect. The amount of time it takes for the motor flux to
dissipate depends upon the size of the drive and motor. If a Start command is issued before the motor flux
has completely dissipated, the HIM will continue to display “Stopped” and the drive will start the motor
after the motor flux has completely dissipated.

Coast Time is load dependent

Stop

Command

Time

Output Voltage

Output Current

Motor Speed

Advertising