Rockwell Automation Publication 20C-PM001F-EN-P - March 2012

47

Programming and Parameters

Chapter 2

CO

MMUNIC

AT

ION

Mas

ks/Ow

ners

288 [Stop Owner]

Adapters that are presently issuing a valid stop command.
1 = Issuing Command
0 = No Command

Read Only

276

thru

285

289 [Start Owner]

Adapters that are presently issuing a valid start
command.

See

[Stop Owner]

.

276

thru

285

290 [Jog Owner]

Adapters that are presently issuing a valid jog
command.

See

[Stop Owner]

.

276

thru

285

291 [Direction Owner]

Adapter that currently has exclusive control of
direction changes.

See

[Stop Owner]

.

276

thru

285

292 [Reference Owner]

Adapter that has the exclusive control of the
command frequency source selection.

See

[Stop Owner]

.

276

thru

285

293 [Accel Owner]

Adapter that has exclusive control of selecting
[Accel Time 1, 2].

See

[Stop Owner]

.

140
276

thru

285

294 [Decel Owner]

Adapter that has exclusive control of selecting
[Decel Time 1, 2].

See

[Stop Owner]

.

142
276

thru

285

295 [Fault Clr Owner]

Adapter that is presently clearing a fault.

See

[Stop Owner]

.

276

thru

285

296 [MOP Owner]

Adapters that are currently issuing increases or
decreases in MOP command frequency.

See

[Stop Owner]

.

276

thru

285

297 [Local Owner]

Adapter that has requested exclusive control of all
drive logic functions. If an adapter is in local
lockout, all other functions (except stop) on all
other adapters are locked out and non-functional.
Local control can only be obtained when the drive
is not running.

See

[Stop Owner]

.

276

thru

285

Da

tal

ink

s

300
301

[Data In A1] - Link A Word 1
[Data In A2] - Link A Word 2

Parameter number whose value will be written
from a communications device data table.
Value will not be updated until drive is stopped.
Refer to your communications option manual for
datalink information.

Default:

Min/Max:
Units:

0 (0 = “Disabled”)

0/486
1

302
303

[Data In B1] - Link B Word 1
[Data In B2] - Link B Word 2

See

[Data In A1] - Link A Word 1 [Data In A2]

- Link A Word 2

.

Fil

e

Gr

oup

No

.

Parameter Name & Description

Values

Rela

ted

Name

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

DPI

P

or

t 6

DPI

P

or

t 5

DPI

P

or

t 4

DPI

P

or

t 3

DPI

P

or

t 2

DPI

P

or

t 1

Di

gi

ta

l I

n

Default

x

x

x

x

x

x

x

x

x

0

0

0

0

0

0

0

Bit

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0