Rockwell Automation Publication 20C-PM001F-EN-P - March 2012

55

Programming and Parameters

Chapter 2

INPUTS/OUT

PUT

S

D

igi

ta

l O

u

tpu

ts

Selected Option Definitions – [Analog Outx Sel], [Digital Inx Sel], [Digital Outx Sel]

381
385
389

[Dig Out1 Level]
[Dig Out2 Level]
[Dig Out3 Level]

Sets the relay activation level for options 10…15
in [Digital Outx Sel]. Units are assumed to match
the above selection (i.e. “At Freq” = Hz, “At
Torque” = Amps).

Default:

Min/Max:
Units:

0.0
0.0
0.0

0.0/1500.0
0.1

380
384
388

382
386
390

[Dig Out1 OnTime]
[Dig Out2 OnTime]
[Dig Out3 OnTime]

Sets the “ON Delay” time for the digital outputs.
This is the time between the occurrence of a
condition and activation of the relay.

Default:

Min/Max:
Units:

0.00 Secs
0.00 Secs
0.00 Secs

0.00/163.00 Secs
0.01 Secs

380
384
388

383
387
391

[Dig Out1 OffTime]
[Dig Out2 OffTime]
[Dig Out3 OffTime]

Sets the “OFF Delay” time for the digital outputs.
This is the time between the disappearance of a
condition and de-activation of the relay.

Default:

Min/Max:
Units:

0.00 Secs
0.00 Secs
0.00 Secs

0.00/163.00 Secs
0.01 Secs

380
384
388

Fil

e

Gr

oup

No

.

Parameter Name & Description

Values

Rela

ted

Option

Description

Related

At Speed

Relay changes state when drive has reached commanded speed.

380 384 388

Excl Link

Links digital input to a digital output if the output is set to “Input 1…6
Link.” This does not need to be selected in the Vector option.

361

…

366

Input 1-6 Link

When Digital Output 1 is set to one of these (i.e. Input 3 Link) in
conjunction with Digital Input 3 set to “Excl Link,” the Digital Input 3
state (on/off) is echoed in the Digital Output 1.

380 384 388

MOP Dec

Decrements speed reference as long as input is closed.

361

…

366

MOP Inc

Increments speed reference as long as input is closed.

361

…

366

Param Cntl (A.O.)

Parameter controlled analog output allows PLC to control analog
outputs through data links. Set in [Anlgx Out Setpt], par. 377…378.

342 345

Param Cntl (D.O.)

Parameter controlled digital output allows PLC to control digital outputs
through data links. Set in [Dig Out Setpt], parameter 379.

380 384 388

PI Reference

Reference for PI block (see

Process PI on page 93

).

342 345

Run Level
RunFwd Level
RunRev Level

Provides a run level input. A run level input does not require a transition
for enable or fault, but does require a transition for a stop.

361

…

366

Run w/Comm

Allows the Comms start bit to operate like a run with the run input on
the terminal block. Ownership rules apply.

361

…

366