Selected Option Definitions – [Analog Outx Sel], [Digital Inx Sel], [Digital Outx Sel]

381
385
389

[Dig Out1 Level]
[Dig Out2 Level]
[Dig Out3 Level]

Sets the relay activation level for options 10…15
in [Digital Outx Sel]. Units are assumed to match
the above selection (i.e. “At Freq” = Hz, “At
Torque” = Amps).

Default:

Min/Max:
Units:

0.0
0.0
0.0

0.0/1500.0
0.1

380
384
388

382
386
390

[Dig Out1 OnTime]
[Dig Out2 OnTime]
[Dig Out3 OnTime]

Sets the “ON Delay” time for the digital outputs.
This is the time between the occurrence of a
condition and activation of the relay.

Default:

Min/Max:
Units:

0.00 Secs
0.00 Secs
0.00 Secs

0.00/163.00 Secs
0.01 Secs

380
384
388

383
387
391

[Dig Out1 OffTime]
[Dig Out2 OffTime]
[Dig Out3 OffTime]

Sets the “OFF Delay” time for the digital outputs.
This is the time between the disappearance of a
condition and de-activation of the relay.

Default:

Min/Max:
Units:

0.00 Secs
0.00 Secs
0.00 Secs

0.00/163.00 Secs
0.01 Secs

380
384
388

Fil

e

Gr

oup

No

.

Parameter Name & Description

Values

Rela

ted

Option

Description

Related

At Speed

Relay changes state when drive has reached commanded speed.

380 384 388

Excl Link

Links digital input to a digital output if the output is set to “Input 1…6
Link.” This does not need to be selected in the Vector option.

361

366

Input 1-6 Link

When Digital Output 1 is set to one of these (i.e. Input 3 Link) in
conjunction with Digital Input 3 set to “Excl Link,” the Digital Input 3
state (on/off) is echoed in the Digital Output 1.

380 384 388

MOP Dec

Decrements speed reference as long as input is closed.

361

366

MOP Inc

Increments speed reference as long as input is closed.

361

366

Param Cntl (A.O.)

Parameter controlled analog output allows PLC to control analog
outputs through data links. Set in [Anlgx Out Setpt], par. 377…378.

342 345

Param Cntl (D.O.)

Parameter controlled digital output allows PLC to control digital outputs
through data links. Set in [Dig Out Setpt], parameter 379.

380 384 388

PI Reference

Reference for PI block (see

Process PI on page 93

).

342 345

Run Level
RunFwd Level
RunRev Level

Provides a run level input. A run level input does not require a transition
for enable or fault, but does require a transition for a stop.

361

366

Run w/Comm

Allows the Comms start bit to operate like a run with the run input on
the terminal block. Ownership rules apply.

361

366