Rockwell Automation 20C PowerFlex 700H Drives Programming User Manual

Page 34

Advertising
background image

34

Rockwell Automation Publication 20C-PM001F-EN-P - March 2012

Chapter 2

Programming and Parameters

DYNAMIC C

O

NTRO

Po

w

er

L

os

s

184 [Power Loss Mode]

Sets the reaction to a loss of input power. Power
loss is recognized when:
DC bus voltage is

73% of [DC Bus Memory]

and [Power Loss Mode] is set to “Coast”.

DC bus voltage is

82% of [DC Bus Memory]

and [Power Loss Mode] is set to “Decel”.

Default:

Options:

0

0
1
2

“Coast”

“Coast”
“Decel”
“Continue”

013
185

185 [Power Loss Time]

Sets the time that the drive will remain in power
loss mode before a fault is issued.

Default:

Min/Max:
Units:

0.5 Secs

0.0/60.0 Secs
0.1 Secs

184

186 [Power Loss Volts]

Sets the level at which the [Power Loss Mode]
selection will occur.

Default:

Min/Max:
Units:

Based on Drive Rated Volts

170.0/780.0 VDC
0.1 VDC

189

[Shear Pin Time]

Sets the time that the drive is at or above current
limit before a fault occurs. Zero disables this
feature.
Note: Added for firmware revision 3.001.

Default:

Min/Max:
Units:

0.0 Secs

0.0/30.0 Secs
0.1 Secs

238

Fil

e

Gr

oup

No

.

Parameter Name & Description

Values

Rela

ted

The drive can use the percentages referenced in [Power Loss Mode] or a trigger point can be set
at [Power Loss Volts]. A digital input (programmed to “29, Pwr Loss Lvl”) is used to toggle
between fixed percentages and the [Power Loss Volts] level.

ATTENTION: Drive damage can occur if proper input impedance is not
provided as explained below. If the value for [Power Loss Volts] is less than
82% of the nominal DC bus voltage, the user must provide a minimum line
impedance to limit inrush current when the power line recovers. The input
impedance should be equal to or greater than the equivalent of a 5%
transformer with a VA rating 5 times the drives input VA rating.

Advertising