Rockwell Automation Publication 20C-PM001F-EN-P - March 2012

33

Programming and Parameters

Chapter 2

D

YNA

MI

C C

O

NT

ROL

Res

ta

rt

Mo

des

178 [Sleep Wake Mode]

Enables/disables the Sleep/Wake function.
Important: When enabled, the following
conditions must be met:
A proper minimum value must be

programmed for [Sleep Level].

A speed reference must be selected in [Speed

Ref A Sel].

At least one of the following must be

programmed (and input closed) in [Digital Inx
Sel]; “Enable,” “Stop=CF,” “Run,” “Run
Forward,” “Run Reverse.”

Note: Option 2 was added for firmware revision
2.001.

Default:

Options:

0

0
1
2

“Disabled”

“Disabled”
“Direct” (Enabled)
“Invert”

168

(1)

When power is cycled, if all conditions are present after power is restored, restart will occur.

(2)

The drive only starts after Sleep Wake Mode is “enabled” and a valid signal is received.

(3)

The active speed reference is determined as explained in “Reference Control” in the Installation Manual. The Sleep/
Wake function and the speed reference may be assigned to the same input.

(4)

Command must be issued from HIM, TB or network.

(5)

Run Command must be cycled.

(6)

Signal does not need to be greater than wake level.

179 [Sleep Wake Ref]

Selects the source of the input controlling the
Sleep Wake function.

Default:

Options:

2

1
2
3-6

“Analog In 2”

“Analog In 1”
“Analog In 2”
“Reserved”

180 [Wake Level]

Defines the analog input level that will start the
drive.

Default:

Min/Max:

Units:

6.000 mA, 6.000 Volts

[Sleep Level]/20.000 mA 10.000
Volts
0.001 mA
0.001 Volts

181

181 [Wake Time]

Defines the amount of time at or above [Wake
Level] before a Start is issued.

Default:

Min/Max:
Units:

0.0 Secs

0.0/1000.0 Secs
0.1 Secs

180

182 [Sleep Level]

Defines the analog input level that will stop the
drive.

Default:

Min/Max:

Units:

5.000 mA, 5.000 Volts

4.000 mA/[Wake Level]
0.000 Volts/[Wake Level]
0.001 mA
0.001 Volts

183

183 [Sleep Time]

Defines the amount of time at or below [Sleep
Level] before a Stop is issued.

Default:

Min/Max:
Units:

0.0 Secs

0.0/1000.0 Secs
0.1 Secs

182

Fil

e

Gr

oup

No

.

Parameter Name & Description

Values

Rela

ted

ATTENTION: Enabling the Sleep Wake function can cause unexpected machine
operation during the Wake mode. Equipment damage and/or personal injury
can result if this parameter is used in an inappropriate application. Do Not use
this function without considering the table below and applicable local, national
& international codes, standards, regulations or industry guidelines.

Conditions Required to Start Drive

(1)(2)(3)

Input

After Power-Up After a Drive Fault

After a Stop Command

Reset by Stop-CF,

HIM or TB

Reset by Clear

Faults (TB)

HIM or TB

Stop

Stop Closed
Wake Signal

Stop Closed
Wake Signal
New Start or Run Cmd.

(4)

Stop Closed
Wake Signal

Stop Closed
Analog Sig. > Sleep Level

(6)

New Start or Run Cmd.

(4)

Enable

Enable Closed
Wake Signal

(4)

Enable Closed
Wake Signal
New Start or Run Cmd.

(4)

Enable Closed
Wake Signal

Enable Closed
Analog Sig. > Sleep Level

(6)

New Start or Run Cmd.

(4)

Run
Run For.
Run Rev.

Run Closed
Wake Signal

New Run Cmd.

(5)

Wake Signal

Run Closed
Wake Signal

New Run Cmd.

(5)

Wake Signal