Rockwell Automation Publication 20C-PM001F-EN-P - March 2012

23

Programming and Parameters

Chapter 2

MOT

O

R CONTROL

To

rq

A

ttribut

es

057 [Flux Up Mode]

Flux is established for [Flux Up Time] before
acceleration.

Default:

Options:

0

0

“Manual”

“Manual”

053
058

058 [Flux Up Time]

Sets the amount of time the drive will use to try
and achieve full motor stator flux. When a Start
command is issued, DC current at current limit
level is used to build stator flux before
accelerating. This will occur unless [Rated Amps]
is less than [Motor NP FLA], then only 81% of
drive rated current is used.

Default:

Min/Max:
Units:

0.2 Secs

0.0/5.0 Secs
0.1 Secs

053
058

059 [SV Boost Filter]

Sets the amount of filtering used to boost voltage
during Sensorless Vector operation.

Default:

Min/Max:
Units:

55

0/32767
1

061 [Autotune]

Provides a manual or automatic method for
setting [IR Voltage Drop], and [Flux Current Ref].
Note: Program parameter 053 [Motor Cntl Sel]
prior to running an autotune.

Default:

Options:

3

0
1
2
3

“Calculate”

“Ready”
“Static Tune”
“Rotate Tune”
“Calculate”

053
062

“Ready” (0) = Parameter returns to this setting following a “Static Tune” or “Rotate Tune.” It also
permits manually setting [IR Voltage Drop], [Ixo Voltage Drop] and [Flux Current Ref].
“Static Tune” (1) = A temporary command that initiates a non-rotational motor stator resistance
test for the best possible automatic setting of [IR Voltage Drop], [Break Voltage] and [Break
Frequency] in all modes. A start command is required within 20 seconds following initiation of
this setting. The parameter returns to “Ready” (0) following the test, at which time another start
transition is required to operate the drive in normal mode. Used when motor cannot be rotated.
“Rotate Tune” (2) = A temporary command that initiates a “Static Tune” followed by a rotational
test for the best possible automatic setting of [Flux Current Ref] and [Start Boost]. A start
command is required following initiation of this setting. The parameter returns to “Ready” (0)
following the test, at which time another start transition is required to operate the drive in
normal mode. Important: Used when motor is uncoupled from the load. Results may not be
valid if a load is coupled to the motor during this procedure.

“Calculate” (3) = This setting uses motor nameplate data to automatically set [IR Voltage Drop],
[Flux Current Ref] and [Slip RPM @ FLA].

062 [IR Voltage Drop]

Value of voltage drop across the resistance of the
motor stator at rated motor current.

Default:

Min/Max:
Units:

Based on Drive Rating

0.0/[Motor NP Volts]

×

0.50

0.1 VAC

053
061

063 [Flux Current Ref]

Value of amps for full motor flux.

Default:

Min/Max:
Units:

Based on Drive Rating

0.00/[Motor NP FLA]
0.01 Amps

053
061

Vo

lt

s p

er

H

er

tz

069 [Start Boost]

Sets the voltage boost level for starting and
acceleration. Refer to parameter 083 [Overspeed
Limit].

Default:

Min/Max:
Units:

Based on Drive Rating

0.0/[Motor NP Volts]

×

0.25

0.1 VAC

053

071 [Break Voltage]

Sets the voltage the drive will output at [Break
Frequency]. Refer to parameter 083 [Overspeed
Limit].

Default:

Min/Max:
Units:

Based on Drive Rating

0.0/[Motor NP Volts]
0.1 VAC

053
072

072 [Break Frequency]

Sets the frequency the drive will output at [Break
Voltage]. Refer to parameter 083.

Default:

Min/Max:
Units:

Based on Drive Rating

0.0/[Maximum Freq]
0.1 Hz

053
071

Fil

e

Gr

oup

No

.

Parameter Name & Description

Values

Rela

ted

ATTENTION: Rotation of the motor in an undesired direction can occur during
this procedure. To guard against possible injury and/or equipment damage, it
is recommended that the motor be disconnected from the load before
proceeding.