Rockwell Automation Publication 20C-PM001F-EN-P - March 2012

73

Troubleshooting

Chapter 3

Table 10 - Over Current Fault (F12) Subcodes

Table 11 - Ground Fault (F13) Subcode

Table 12 - Load Loss Fault (F15) Subcode

Table 13 - Input Phase Fault (F17) Subcodes

9047

A supply voltage hardware problem has been detected on the 20C-DG1 option
board.

Replace the 20C-DG1 option board.

9303

A supply voltage hardware problem has been detected on the 20C-DG1 option
board.

Replace the 20C-DG1 option board.

9559

A single hardware problem has been detected in the safe disable inputs on the
20C-DG1 option board.

Replace the 20C-DG1 option board.
If this fault occurs again, replace the Main Control board.

9815

A single hardware problem has been detected in the safe disable inputs on the
20C-DG1 option board.

Replace the 20C-DG1 option board. If this fault occurs again, replace the Main Control
board.

10071

A single hardware problem has been detected in the safe disable inputs on the
20C-DG1 option board.

Replace the 20C-DG1 option board. If this fault occurs again, replace the Main Control
board.

10327

A single hardware problem has been detected in the safe disable inputs on the
20C-DG1 option board.

Replace the 20C-DG1 option board. If this fault occurs again, replace the Main Control
board.

10583

A single hardware problem has been detected in the thermistor input on the
20C-DG1 option board.

Replace the 20C-DG1 option board.

10839

A single hardware problem has been detected in the thermistor input on the
20C-DG1 option board.

Replace the 20C-DG1 option board.

11096

A single hardware problem has been detected in the thermistor input on the
20C-DG1 option board.

Replace the 20C-DG1 option board.

11351

A single hardware problem has been detected in the safe disable inputs or in the
thermistor input on the 20C-DG1 option board.

Replace the 20C-DG1 option board. If this fault occurs again, replace the Main Control
board.

11607

A single hardware problem has been detected in the safe disable inputs or in the
thermistor input on the 20C-DG1 option board.

Replace the 20C-DG1 option board. If this fault occurs again, replace the Main Control
board.

11863

A single hardware problem has been detected in the safe disable inputs or in the
thermistor input on the 20C-DG1 option board.

Replace the 20C-DG1 option board. If this fault occurs again, replace the Main Control
board.

12119

The 20C-DG1 option board has been mounted in an incompatible Main Control
board that is not equipped with the Safe Disable function.

Replace the Main Control board.

12376

Parameter expander board, slot B, Therm Trip is set to OFF even if the jumper X12 is not cut.

Subcode

Description

Action

Subcode

Description

272, 273

There is an over current in the power unit.

275

There is an over current in the U phase of the power unit (typically frame 11 and 13 drives).

276

There is an over current in the V phase of the power unit (typically frame 11 and 13 drives).

277

There is an over current in the W phase of the power unit (typically frame 11 and 13 drives).

288, 289

There is an over current in power unit 1 (typically frame 12 drives).

291

There is an over current in the U phase of power unit 1 (typically frame 14 drives).

292

There is an over current in the V phase of power unit 1 (typically frame 14 drives).

293

There is an over current in the W phase of power unit 1 (typically frame 14 drives).

304, 305

There is an over current in power unit 2 (typically frame 12 drives).

307

There is an over current in the U phase of power unit 2 (typically frame 14 drives).

308

There is an over current in the V phase of power unit 2 (typically frame 14 drives).

309

There is an over current in the W phase of power unit 2 (typically frame 14 drives).

Subcode

Description

273

There is a ground fault in the power unit.

Subcode

Description

400

The motor underload protection has tripped.

Subcode

Description

273

One input line phase in the power unit is missing.