Chapter 2

Programming and Parameters

SPEED C

O

MMAND

Pr

oc

ess

P

I

124 [PI Configuration]

Sets configuration of the PI regulator.
Note: Added bit 9 “% of Ref” for firmware revision 3.001.
1 = Enabled
0 = Disabled

124

thru

138

125 [PI Control]

Controls the PI regulator.
1 = Enabled
0 = Disabled

080

126 [PI Reference Sel]

Selects the source of the PI reference.

Default:

Options:

0

0
1
2
3-8
9
10
11-17
18-22

“PI Setpoint”

“PI Setpoint”
“Analog In 1”
“Analog In 2”
“Reserved”
“MOP Level”
“Master Ref”
“Preset Spd1-7”
“DPI Port 1-5”

124

thru

138

127 [PI Setpoint]

Provides an internal fixed value for process
setpoint when [PI Reference Sel] is set to “PI
Setpoint.”

Default:

Min/Max:

Units:

50.0%

–/+100.0% of Maximum
Process Value
0.1%

124

thru

138

128 [PI Feedback Sel]

Selects the source of the PI feedback.

Default:

Options:

2

“Analog In 2”

See

[PI Reference Sel]

.

124

thru

138

129 [PI Integral Time]

Time required for the integral component to reach
100% of [PI Error Meter]. Not functional when the
PI Hold bit of [PI Control] = “1” (enabled).

Default:

Min/Max:
Units:

2.0 Secs

0.00/100.00 Secs
0.01 Secs

124

thru

138

130 [PI Prop Gain]

Sets the value for the PI proportional component.
PI Error x PI Prop Gain = PI Output

Default:

Min/Max:
Units:

1.0

0.00/100.00
0.01

124

thru

138

131 [PI Lower Limit]

Sets the lower limit of the PI output.

Default:

Min/Max:
Units:

–[Maximum Freq]
100%

–/+800.0%
0.1%

079
124

thru

138

132 [PI Upper Limit]

Sets the upper limit of the PI output.

Default:

Min/Max:
Units:

+[Maximum Freq]
100%

–/+800.0%
0.1%

079
124

thru

138

Fil

e

Gr

oup

No

.

Parameter Name & Description

Values

Rela

ted

Name

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

% of Ref

Re

se

rv

ed

An

ti-

W

ind Up

St

op Mode

Feed

bak S

qr

t

Ze

ro

C

la

m

p

Ra

m

p R

ef

Pr

eload

Mode

In

ve

rt

E

rr

or

Ex

cl

M

od

e

Default

x

x

x

x

x

x

0

x

0

0

0

0

0

0

0

0

Bit

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Name

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

PI

Re

se

t

PI

H

old

PI

E

na

ble

Default

x

x

x

x

x

x

x

x

x

x

x

x

x

0

0

0

Bit

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Advertising