Rockwell Automation 20C PowerFlex 700H Drives Programming User Manual

Page 53

Advertising
background image

Rockwell Automation Publication 20C-PM001F-EN-P - March 2012

53

Programming and Parameters

Chapter 2

INPUTS/OUT

PUT

S

Digi

tal In

put

s

361
362
363
364
365
366

[Digital In1 Sel]
[Digital In2 Sel]
[Digital In3 Sel]
[Digital In4 Sel]
[Digital In5 Sel]
[Digital In6 Sel]

(9)

Selects the function for the digital inputs.
Notes: Options 36…42 are “Reserved”. Added
options 43 and 46 for firmware revision 3.001.
Added options 41, 42, 44 and 45 for firmware
revision 4.001. Added option 68 for firmware
revision 5.002.

(1)

Speed Select Inputs.

To access Preset Speed 1, set [Speed Ref x Sel] to
“Preset Speed 1”.

Type 2 Alarms - Some digital input programming
may cause conflicts that will result in a Type 2
alarm. Example: [Digital In1 Sel] set to “5, Start” in
3-wire control and [Digital In2 Sel] set to 7 “Run”
in2-wire.

Refer to

Table 1 on page 64

for information on

resolving this type of conflict.

(2)

When [Digital Inx Sel] is set to option 2 “Clear
Faults” the Stop button cannot be used to clear a
fault condition.

(3)

Typical 3-Wire Inputs - Requires that only 3-wire
functions are chosen. Including 2-wire selections
will cause a type 2 alarm.

(4)

Typical 2-Wire Inputs - Requires that only 2-wire
functions are chosen. Including 3-wire selections
will cause a type 2 alarm. See

Table 1 on page 64

for conflicts.

(5)

Auto/Manual - Refer to the Installation Manual for
details.

(6)

Opening an “Enable” input will cause the motor to
coast-to-stop, ignoring any programmed Stop
modes.

Default:
Default:
Default:
Default:
Default:
Default:

Options:

4
5
18
15
16
17

0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30-33
34
35
36-40
41
42
43
44
45
46
68

“Stop – CF”
“Start”
“Auto/ Manual”
“Speed Sel 1”
“Speed Sel 2”
“Speed Sel 3”

“Not Used”
“Enable”

(6)(8)

“Clear Faults”(CF)

(2)

“Aux Fault”
“Stop – CF”

(8)

“Start”

(3)(7)

“Fwd/ Reverse”

(3)

“Run”

(4)(8)

“Run Forward”

(4)

“Run Reverse”

(4)

“Jog1”

(3)

“Jog Forward”

(4)

“Jog Reverse”

(4)

“Stop Mode B”
“Bus Reg Md B”
“Speed Sel 1”

(1)

“Speed Sel 2”

(1)

“Speed Sel 3”

(1)

“Auto/ Manual”

(5)

“Local”
“Acc2 & Dec2”
“Accel 2”
“Decel 2”
“MOP Inc”

(10)

“MOP Dec”

(10)

“Excl Link”

(10)

“PI Enable”
“PI Hold”
“PI Reset”
“Pwr Loss Lvl”
Reserved
“Jog 2”
“PI Invert”
“Reserved”
“UserSet Sel1”

(10)

“UserSet Sel2”

(10)

“Run Level”

(11)

“RunFwd Level”

(11)

“RunRev Level”

(11)

“Run w/Comm”

(11)

“Manual/Auto”

(12)

100

156
162

096

141
143
195

194

124

(7)

A “Dig In ConflictB” alarm will occur if a “Start” input is programmed without a “Stop” input.

(8)

Refer to the Sleep Wake Mode Attention statement on

page 33

.

(9)

A dedicated hardware enable input is available via a jumper selection. Refer to Installation Manual for
further information.

(10)

Refer to [Dyn UsrSet Sel] on

page 37

for selection information.

(11)

Refer to

Selected Option Definitions – [Analog Outx Sel], [Digital Inx Sel], [Digital Outx Sel] on page 55

.

(12)

The function of this value is similar to 18 “Auto/Manual”, except the polarity is opposite.

Fil

e

Gr

oup

No

.

Parameter Name & Description

Values

Rela

ted

3

2

1

Auto Reference Source

0
0
0
0
1
1
1
1

0
0
1
1
0
0
1
1

0
1
0
1
0
1
0
1

Reference A
Reference B
Preset Speed 2
Preset Speed 3
Preset Speed 4
Preset Speed 5
Preset Speed 6
Preset Speed 7