Dynamic control file – Rockwell Automation 20C PowerFlex 700H Drives Programming User Manual

Page 30

Advertising
background image

30

Rockwell Automation Publication 20C-PM001F-EN-P - March 2012

Chapter 2

Programming and Parameters

Dynamic Control File

Fil

e

Gr

ou

p

No

.

Parameter Name & Description

Values

Rela

ted

D

YNA

MI

C C

O

NT

ROL

Ra

mp Ra

te

s

140
141

[Accel Time 1]
[Accel Time 2]

Sets rate of accel for all speed increases.

Default:

Min/Max:
Units:

10.0 Secs
10.0 Secs

0.1/3276.7 Secs
0.1 Secs

142
143
146
361

thru

366

142
143

[Decel Time 1]
[Decel Time 2]

Sets rate of decel for all speed decreases.

Default:

Min/Max:
Units:

10.0 Secs
10.0 Secs

0.1/3276.7 Secs
0.1 Secs

140
141
146
361

thru

366

146 [S Curve %]

Sets the percentage of accel or decel time that is
applied to the ramp as S Curve. Time is added, 1/2
at the beginning and 1/2 at the end of the ramp.

Default:

Min/Max:
Units:

0%

0/100%
1%

140

thru

143

Load Limits

147 [Current Lmt Sel]

Selects the source for the adjustment of current
limit (i.e. parameter, analog input, etc.).

Default:

Options:

0

0
1
2

“Cur Lim Val”

“Cur Lim Val”
“Analog In 1”
“Analog In 2”

146
149

148 [Current Lmt Val]

Defines the current limit value when [Current Lmt
Sel] = “Cur Lim Val.”

Default:

Min/Max:
Units:

Based on Drive Rating

Based on Drive Rating
0.1 Amps

147
149

149 [Current Lmt Gain]

Sets the responsiveness of the current limit.

Default:

Min/Max:
Units:

10000

0/32767
1

147
148

150 [Drive OL Mode]

Selects drive response to increasing drive
temperature.

Default:

Options:

3

0
1
2
3

“Both-PWM 1st”

“Reserved”
“Reduce Clim”
“Reserved”
“Both-PWM 1st”

151 [PWM Frequency]

Sets the carrier frequency for the PWM output.
Drive derating may occur at higher carrier
frequencies.

Default:

Min/Max:
Units:

1.5 kHz or 2 kHz based on Drive
Rating

1/Based on Drive Rating
1 kHz

152 [Droop RPM @ FLA]

Selects amount of droop that the speed reference
is reduced when at full load torque. Zero disables
the droop function.

Important: Selecting “Slip Comp” with
parameter 080 in conjunction with parameter
152, may produce undesirable results.

Default:

Min/Max:
Units:

0.0 RPM

0.0/200.0 RPM
0.1 RPM

Stop/Bra

ke

M

ode

s

145 [DB While Stopped]

Enables/disables dynamic brake operation when
drive is stopped. DB may operate if input voltage
becomes too high.
Disabled = DB will not operate when the drive

is stopped.

Enabled = DB may operate whenever drive is

energized.

Notes: This parameter is used for frame 9 drives
only. Added for firmware revision 3.001.

Default:

Options:

0

0
1

“Disabled”

“Disabled”
“Enabled”

Max Speed

Accel Time

Accel Rate

=

Max Speed
Decel Time

Decel Rate

=