Troubleshooting

Chapter 3

10

System Fault

2

One of the following has occurred:
A hardware problem exists in

the power structure.
See

Table 9, “System Fault (F10)

Subcodes,” on page 72

for more

information on this fault.
Note: Subcodes are only
available in revision 4.001 or
later.

1. Cycle the power.
2. Verify the fiber optic connections.
3. Contact Technical Support. See

Technical

Support Options on page 79

for more

information. If the problem persists,
replace the drive.

The 20C-DG1 option board has

been removed.
See

Table 9, “System Fault (F10)

Subcodes,” on page 72

for more

information on this fault.
Note: Subcodes are only
available in revision 4.001 or
later.

Set parameter 358 [20C-DG1 Remove] to
1"Remove” and then back to 0 “Ready” to
clear and acknowledge the fault. Once
maintenance or service is completed and the
20C-DG1 option card has been reinstalled,
the drive will recognize the option card on
power-up.

12

OverCurrent

1

The drive output current has
instantaneously exceeded 360% of
the HD rating.
See

Table 10, “Over Current Fault

(F12) Subcodes,” on page 73

for

more information on this fault.

Check programming for an excess load,
improper DC boost setting, DC brake voltage
set too high or other causes of excess
current. Check for shorted motor leads or a
shorted motor.

13

Ground Fault

1

A current path to earth ground
exists that is greater than 50% of
the drive's heavy duty rating. The
current must appear for 800ms
before the drive will fault.
See

Table 11, “Ground Fault (F13)

Subcode,” on page 73

for more

information on this fault.

Check the motor and external wiring to the
drive output terminals for a grounded
condition.

14

InverterFault

2

A hardware problem exists in the
power structure.

1. Cycle the power.
2. Contact Technical Support. See

Technical

Support Options on page 79

for more

information.

3. If the problem persists, replace the drive.

15

Load Loss

3

1 Do not use this fault in PowerFlex

700H applications.
See

Table 12, “Load Loss Fault (F15)

Subcode,” on page 73

for more

information on this fault.

Parameter 238 [Fault Config 1] / bit 0
“Power Loss” and parameter 259 [Alarm
Config 1] / bit 13 “Load Loss” are set to zero.

16

Motor Therm

3

1 The option board thermistor input

is greater than the limit.

1. Check to ensure that the motor is cooling

properly.

2. Check for an excess load.
3. Verify the thermistor connection. If the

thermistor connection on the option
board is not used, it must be shorted.

17

Input Phase

3

1 One input line phase is missing.

See

Table 13, “Input Phase Fault

(F17) Subcodes,” on page 73

for

more information on this fault.

1. Check all user-supplied fuses
2. Check the AC input line voltage.

19

Unbalanced

2

An imbalance between the power
modules exists (paralleled units -
frames 12 & 14 only).

1. Check for DC voltage imbalance between

the power modules.

2. Check for current output imbalance

between the power modules.

21

OutPhasMissng

2

There is zero current in one of the
output motor phases.
See

Table 14, “Output Phase

Missing Fault (F21) Subcode,” on
page 74

for more information on

this fault.

1. Check the motor wiring.
2. Check the motor for an open phase.

22

NP Hz Cnflct

2 The “fan/pump” mode is selected in [Motor Cntl Sel] and the ratio of parameter 43

[Motor NP Hertz] to 55 [Maximum Freq] is greater than 26.

No. Name

Fa

u

lt

Alarm

Description

Action (if applicable)