Fault subcodes, Table 3, “precharge active fault, Table 4, “under voltage fault – Rockwell Automation 20C PowerFlex 700H Drives Programming User Manual

Page 71: Table 5, “over voltage fault, Table 6, “motor stall fault (f6), Table 7, “heatsink over, For mor

Advertising
background image

Rockwell Automation Publication 20C-PM001F-EN-P - March 2012

71

Troubleshooting

Chapter 3

Fault Subcodes

Fault Subcodes can be viewed in parameters 543, 545, 547, 549, 551, 553, 555,
and 557 [Fault

x Subcode]. Each of these parameters corresponds with

parameters 243, 245, 247, 249, 251, 253, 255, and 257 [Fault

x Code],

respectively. For example, if parameter 243 [Fault 1 Code] displays “5” and
parameter 543 [Fault 1 Subcode] displays “273”, an over voltage fault (F5) has
occurred in the power unit of the drive.

Table 3 - Precharge Active Fault (F1) Subcodes

Table 4 - Under Voltage Fault (F4) Subcodes

Table 5 - Over Voltage Fault (F5) Subcodes

Table 6 - Motor Stall Fault (F6) Subcode

Table 7 - Heatsink Over Temperature Fault (F8) Subcodes

IGBT OverTemp

9

UnderVoltage

4

IGBT Temp Hw

31

UserSetCflct

139

Input Phase

17

UserSet Timer

99

IntDB OvrHeat

148

VHz Neg Slope

26

InverterFault

14

Waking

149

Load Loss

15

Zero Divide

54

Name

No.

Fa

u

lt

Alarm

Name

No.

Fa

u

lt

Alarm

Subcode

Description

273

The precharge circuit in the power unit is active.

289

The precharge circuit in power unit 1 is active.

305

The precharge circuit in power unit 2 is active.

Subcode

Description

273

The DC Bus voltage in the power unit is too low while the drive is in a run state.

529

The DC Bus voltage in the power unit is too low while the drive is in a run state.

545

The DC Bus voltage in power unit 1 is too low while the drive is in a run state.

561

The DC Bus voltage in power unit 2 is too low while the drive is in a run state.

785

The DC Bus voltage in the power unit fell too low during a fast stop.

Subcode

Description

273

There is an over voltage in the power unit.

289

There is an over voltage in power unit 1.

276

There is an over voltage in power unit 2.

277

There is an over voltage in the power unit.

Subcode

Description

400

The motor is operating at high current and low frequency and is not accelerating.

Subcode

Description

272, 273

There is a heatsink over temperature in the power unit.

274

There is a heatsink over temperature on the Power board of the power unit.

275

There is a heatsink over temperature in the U phase of the power unit (typically frame 11 and 13 drives).

276

There is a heatsink over temperature in the V phase of the power unit (typically frame 11 and 13 drives).

277

There is a heatsink over temperature in the W phase of the power unit (typically frame 11 and 13 drives).

288, 289

There is a heatsink over temperature in power unit 1 (typically frame 12 and 14 drives).

290

There is a heatsink over temperature on the Power board of power unit 1 (typically frame 12 and 14 drives).

291

There is a heatsink over temperature in the U phase of power unit 1 (typically frame 12 and 14 drives).

292

There is a heatsink over temperature in the V phase of power unit 1 (typically frame 12 and 14 drives).