Table 22, “nvs read checksum, Table 24, “power unit fault, Table 25, “hardware enable – Rockwell Automation 20C PowerFlex 700H Drives Programming User Manual

Page 76: Table 26, “parameter checksum, Table 27, “main control board

Advertising
background image

76

Rockwell Automation Publication 20C-PM001F-EN-P - March 2012

Chapter 3

Troubleshooting

Table 22 - NVS Read Checksum Fault (F47) Subcode

Table 23 - Motor Over Temperature Fault (F16) Subcode

Table 24 - Power Unit Fault (F70) Subcodes

Table 25 - Hardware Enable Fault (F94) Subcode

Table 26 - Parameter Checksum Fault (F100) Subcodes

Table 27 - Main Control Board - Power Board Configuration Fault (F106) Subcode

370

The Star Coupler board has been changed, added, removed, has experienced a checksum error, or is new
and the parameters for the device/board remain unchanged (typically frame 12 and 14 drives).

528

The power level in power unit 2 is not equal to the power level in power unit 1 after a microprocessor reset
(typically frame 12 and 14 drives).

561

The power level in power unit 2 is not equal to the power level in power unit 1 after a microprocessor reset
(typically frame 12 and 14 drives).

Subcode

Description

322

An operating time or energy counter checksum error has occurred on the Control board.

Subcode

Description

400

The motor is operating at high current and low frequency and is not accelerating.

Subcode

Description

272, 273

There is saturation in the power unit.

275

There is saturation in the U phase of the power unit (typically frame 11 and 13 drives).

276

There is saturation in the V phase of the power unit (typically frame 11 and 13 drives).

277

There is saturation in the W phase of the power unit (typically frame 11 and 13 drives).

288, 289

There is saturation in power unit 1 (typically frame 12 and 14 drives).

291

There is saturation in the U phase of power unit 1 (typically frame 14 drives).

292

There is saturation in the V phase of power unit 1 (typically frame 14 drives).

293

There is saturation in the W phase of power unit 1 (typically frame 14 drives).

304, 305

There is saturation in power unit 2 (typically frame 12 and 14 drives).

307

There is saturation in the U phase of power unit 2 (typically frame 14 drives).

308

There is saturation in the V phase of power unit 2 (typically frame 14 drives).

309

There is saturation in the W phase of power unit 2 (typically frame 14 drives).

Subcode

Description

338

An hardware enable signal is missing from the control terminal block.

Subcode

Description

322

A firmware interface power down variable checksum error has occurred on the Control board.

578

A firmware interface variable checksum error has occurred on the Control board.

834

A system powerdown variable checksum error (panel menu index, fault history pointer) has occurred on
the Control board.

1090

A system parameter checksum error (multimonitor, panel default pages) has occurred on the Control
board.

1346

An application defined powerdown, variable checksum error has occurred on the Control board.

1602

An application defined powerdown, variable checksum error has occurred on the Control board.

2626

A system parameter checksum error (fault history entries, device valid, system menu parameters) has
occurred on the Control board.

Subcode

Description

385

The software and the power unit are incompatible.

Subcode

Description