Table 8 - IGBT Over Temperature Fault (F9) Subcode

Table 9 - System Fault (F10) Subcodes

293

There is a heatsink over temperature in the W phase of power unit 1 (typically frame 12 and 14 drives).

304, 305

There is a heatsink over temperature in power unit 2 (typically frame 12 and 14 drives).

306

There is a heatsink over temperature on the Power board of power unit 2 (typically frame 12 and 14 drives).

307

There is a heatsink over temperature in the U phase of power unit 2 (typically frame 12 and 14 drives).

308

There is a heatsink over temperature in the V phase of power unit 2 (typically frame 12 and 14 drives).

309

There is a heatsink over temperature in the W phase of power unit 2 (typically frame 12 and 14 drives).

530

There is a Thermistor over temperature on the Power board (typically frame 12 and 14 drives).

Subcode

Description

273

The output transistors have exceeded their maximum operating temperature due to an excessive load.

Subcode

Description

Subcode

Description

Action

273

There is an output phase feedback fault from the motor cables.

275

There is an output phase feedback fault from the U phase motor cable (typically frame 11 and 13 drives).

276

There is an output phase feedback fault from the V phase motor cable (typically frame 11 and 13 drives).

277

There is an output phase feedback fault from the W phase motor cable (typically frame 11 and 13 drives).

1042

There is a disturbance at the ASIC fault-input of the Power board - ribbon cable/software.

1058

There is a disturbance at the ASIC fault-input of the Power board in power unit 1 - ribbon cable/software (typically frame 12 and 14 drives).

1074

There is a disturbance at the ASIC fault-input of the Power board in power unit 2 - ribbon cable/software (typically frame 12 and 14 drives).

1090

There is a disturbance at the ASIC fault-input of the Control board - application software.

1298

There is too much disturbance in system bus traffic on the Power board.

1314

There is too much disturbance in system bus traffic on the Power board in power unit 1 (typically frame 12 and 14 drives).

1330

There is too much disturbance in system bus traffic on the Power board in power unit 2 (typically frame 12 and 14 drives).

1553

The charging relay feedback is not working.

1810

The charging relay control is not set on the Power board.

1826

The charging relay control is not set on the Power board on power unit 1 (typically frame 12 and 14 drives).

1827

The charging relay control is not set configured on the Power board on power unit 2 (typically frame 12 and 14 drives).

2065

The Gate Driver board is without auxiliary voltage (Power ASIC-TRIN).

2067

The Gate Driver board for the U phase is without auxiliary voltage (typically frame 11 and 13 drives).

2068

The Gate Driver board for the V phase is without auxiliary voltage (typically frame 11 and 13 drives).

2069

The Gate Driver board for the W phase is without auxiliary voltage (typically frame 11 and 13 drives).

2080

The Gate Driver board in power unit 1 is without auxiliary voltage. (typically frame 11 and 13 drives).

2081

The Gate Driver board in power unit 1 is without auxiliary voltage (typically frame 12 and 14 drives).

2083

The Gate Driver board for the U phase in power unit 1 is without auxiliary voltage (typically frame 14 drives).

2084

The Gate Driver board for the V phase in power unit 1 is without auxiliary voltage (typically frame 14 drives).

2085

The Gate Driver board for the W phase in power unit 1 is without auxiliary voltage (typically frame 14 drives).

2097

The Gate Driver board in power unit 2 is without auxiliary voltage (typically frame 12 and 14 drives).

2099

The Gate Driver board for the U phase in power unit 2 is without auxiliary voltage (typically frame 14 drives).

2100

The Gate Driver board for the V phase in power unit 2 is without auxiliary voltage (typically frame 14 drives).

2101

The Gate Driver board for the W phase in power unit 2 is without auxiliary voltage (typically frame 14 drives).

2370

The TX fiber optic cable connected to H6 on the 700H Control board is broken.

2594

The fiber optic cable connected to TRIP on the Star Coupler board for power unit 1 is broken (typically frame 12 and 14 drives).

2610

The fiber optic cable connected to TRIP on the Star Coupler board for power unit 2 is broken (typically frame 12 and 14 drives).

2834

The fiber optic cable connected to H5 on the ASIC board is broken.

7767

The safe disable inputs on the 20C-DG1 option board have been in a different
state for more than 5 seconds.

Verify all connections to the 20C-DG01 option board.
If this fault and subcode occurs again, replace the 20C-DG1 option board.

8023

A thermistor short circuit has been detected on the 20C-DG1 option board.

Verify the thermistor connections and correct if necessary.
Verify that the jumper at X10 is in the correct position.

8279

The 20C-DG1 option board has been removed.

Set parameter 359 [20C-DG1 Status] to 1"Remove" and then back to 0 "Ready".

8535

There is an EEPROM error on the 20C-DG1 option board.

Replace the 20C-DG1 option board.

8791

A supply voltage hardware problem has been detected on the 20C-DG1 option
board.

Replace the 20C-DG1 option board.