Rockwell Automation 20C PowerFlex 700H Drives Programming User Manual

Page 32

Advertising
background image

32

Rockwell Automation Publication 20C-PM001F-EN-P - March 2012

Chapter 2

Programming and Parameters

DYNAMI

C C

O

NTRO

L

Stop/B

rak

e Mo

des

164 [Bus Reg Kp]

Proportional gain for the bus regulator. Used to
adjust regulator response.

Default:

Min/Max:
Units:

Based on Drive Rating

0/10000
1

165 [Bus Reg Kd]

Derivative gain for the bus regulator. Used to
control regulator overshoot.

Default:

Min/Max:
Units:

122

0/10000
1

465 [Fan Control]

Enables/Disables the drive cooling fan control.
“Disabled” = Drive cooling fan control off - fan(s)
always runs
“Enabled” = Drive cooling fan control on - the
cooling fan(s) stops if the drive is stopped and the
heatsink temperature is below 55

°

C for 60

seconds
Note: Added for firmware revision 4.001. Changed
the default value to 1 “Enabled” for firmware
revision 6.001.

Default:

Options:

1

0
1

“Enabled”

“Disabled”
“Enabled”

Res

tar

t Mo

des

167 [Powerup Delay]

Defines the programmed delay time, in seconds,
before a start command is accepted after a power
up.

Default:

Min/Max:
Units:

0.0 Secs

0.0/30.0 Secs
0.1 Secs

168 [Start At PowerUp]

Enables/disables a feature to issue a Start or Run
command and automatically resume running at
commanded speed after drive input power is
restored. Requires a digital input configured for
Run or Start and a valid start contact.

Default:

Options:

0

0
1

“Disabled”

“Disabled”
“Enabled”

169 [Flying Start En]

Enables/disables the function which reconnects
to a spinning motor at actual RPM when a start
command is issued.

Default:

Options:

0

0
1

“Disabled”

“Disabled”
“Enabled”

174 [Auto Rstrt Tries]

Sets the maximum number of times the drive
attempts to reset a fault and restart.

Default:

Min/Max:
Units:

0

0/9
1

175

175 [Auto Rstrt Delay]

Sets the time between restart attempts when
[Auto Rstrt Tries] is set to a value other than zero.

Default:

Min/Max:
Units:

1.0 Secs

0.5/30.0 Secs
0.1 Secs

174

Fil

e

Gr

oup

No

.

Parameter Name & Description

Values

Rela

ted

ATTENTION: Equipment damage and/or personal injury may result if this
parameter is used in an inappropriate application. Do not use this function
without considering applicable local, national and international codes,
standards, regulations or industry guidelines.

ATTENTION: Equipment damage and/or personal injury may result if this
parameter is used in an inappropriate application. Do not use this function
without considering applicable local, national and international codes,
standards, regulations or industry guidelines.