Rockwell Automation 20C PowerFlex 700H Drives Programming User Manual

Page 70

Advertising
background image

70

Rockwell Automation Publication 20C-PM001F-EN-P - March 2012

Chapter 3

Troubleshooting

Table 2 - Fault/Alarm Cross Reference

135 DigIn CnflctC

2 More than one physical input has been configured to the same input function.

Multiple configurations are not allowed for the following input functions.
Fwd/Rev

Run Reverse

Bus Reg Md B

UserSet Sel2

Speed Sel 1

Jog Forward

Acc2 & Dec2

Run Level

Speed Sel 2

Jog Reverse

Accel 2

RunFwd Level

Speed Sel 3

Run

Decel 2

RunRev Level

Run Forward

Stop Mode B

UserSet Sel1

Run w/Comm

136 BipolarCnflct

2 Parameter 190 [Direction Mode] is set to “Bipolar” or “Reverse Dis” and one or

more of the following digital input functions is configured: “Fwd/Reverse,” “Run
Forward,” “Run Reverse,” “Jog Forward” or “Jog Reverse.”

139 UserSetCflct

2 Not all digital inputs and datalinks in the user set you are saving are the same. All

user sets must be saved with the same settings for parameters 361-366, 300-307
and 310-317.

143 TB Man Conflict

2 Parameter 96 [TB Man Ref Sel] is

using an analog input that is
programmed for another function.

Check the parameter settings to avoid
problem.

147 Start AtPwrUp

1 Parameter 168 [Start At PowerUp] is enabled. The drive may start at any time

within 10 seconds of drive powerup.

148 IntDB OvrHeat

1 The drive has temporarily disabled the DB regulator because the resistor

temperature has exceeded a predetermined value.

149 Waking

1 The Wake timer is counting toward a value that will start the drive.

150 Sleep Config

2 Sleep/Wake configuration error. With parameter 178 [Sleep Wake Mode] =

“Direct,” possible causes include: drive is stopped and parameter 180 [Wake Level]
< parameter 182 [Sleep Level].“Stop=CF,” “Run,” “Run Forward,” or “Run
Reverse” is not configured in [Digital Inx Sel].

Name

No.

Fa

u

lt

Al

arm

Name

No.

Fa

u

lt

Al

arm

Anlg In Loss

29

MaxFreqCnflct

23

AutoReset Lim

33

MCB-PB Config

106

AutoT Enable

114

MicroWatchdog

30

AutoT Lm Rot

96

Motor Stall

6

AutoT MagRot

97

Motor Therm

16

AutoT Rs Stat

95

MotorCalcData

50

AutoT Saturat

98

MotorOverload

7

Auxiliary In

2

New IO Option

107

BipolarCnflct

136

NP Hz Cnflct

22

BrakResMissng

28

NvsReadChksum

47

CAN Bus Flt

34

OutPhasMissng

21

Decel Inhibit

24

OverCurrent

12

Device Add

45

OverSpd Limit

25

Device Change

44

OverVoltage

5

DigIn CnflctA

133

Param Chksum

100

DigIn CnflctB

134

ParamsDefault

48

DigIn CnflctC

135

Periph Loss

71

Fan Cooling

32

Port DPI Loss

81

Fatal App

113

Power Loss

3

Gate Disable

59

Power Unit

70

Ground Fault

13

PrechargeActv

1

Hardware Enbl

94

PwrBrd Chksum

104

HeatsinkOvrTp

8

Shear Pin

63

HeatsinkUndTp

37

Sleep Config

150

Hrdwr Therm

60

SpdRef Cnflct

27

I/O Change

120

Start AtPwrUp

147

I/O Comm Loss

121

System Fault

10

I/O Removed

65

TB Man Conflict

143

No. Name

Fa

u

lt

Alarm

Description

Action (if applicable)