Rockwell Automation 20C PowerFlex 700H Drives Programming User Manual

Page 67

Advertising
background image

Rockwell Automation Publication 20C-PM001F-EN-P - March 2012

67

Troubleshooting

Chapter 3

34

CAN Bus Flt

2

A sent message was not
acknowledged.
See

Table 19, “Communication Bus

Fault (F34) Subcode,” on page 74

for more information on this fault.

1. Cycle the power.
2. Replace the Main Control board.

37

HeatsinkUndTp

1

The ambient temperature is too
low.
See

Table 20, “Heatsink Under

Temperature Fault (F37) Subcodes,”
on page 75

for more information on

this fault.

Raise the ambient temperature.

44

Device Change

2

The new power unit or option
board installed is a different type.
See

Table 21, “Device Change (F44),

Device Added (F45), I/O Option
Board Removed (F65), Power Board
Checksum (F104), New I/O Option
Board (F107) and I/O Option Board
Change (F120) Fault Subcodes,” on
page 75

for more information on

this fault.

Clear the fault and reset the drive to the
factory defaults.

45

Device Add

2

A new option board was added.
See

Table 21, “Device Change (F44),

Device Added (F45), I/O Option
Board Removed (F65), Power Board
Checksum (F104), New I/O Option
Board (F107) and I/O Option Board
Change (F120) Fault Subcodes,” on
page 75

for more information on

this fault.

Clear the fault.

47

NvsReadChksum

2

There was an error reading
parameters 9 [Elapsed MWh] and
10 [Elapsed Run Time] from
EEPROM.
See

Table 22, “NVS Read Checksum

Fault (F47) Subcode,” on page 76

for more information on this fault.

1. Cycle the power.
2. Replace the Main Control board.

48

ParamsDefault

2

The drive was commanded to write
default values to EEPROM.

1. Clear the fault or cycle power to the

drive.

2. Program the drive parameters as needed.

54

Zero Divide

2

This event occurred because a
mathematical function had a
dividend of zero.

1. Cycle the power.
2. Replace the main Control board.

59

Gate Disable

3

1 Both of the digital gate disable

inputs (SD-1 and SD-2) are not
enabled on the 20C-DG1 option
board.

1. Check the motor.
2. Verify that the option board is properly

wired.

3. Replace the option board. See Appendix

E - “Instructions for ATEX Approved
PowerFlex 700H Drives in Group II
Category (2) Applications with ATEX
Approved Motors” in the PowerFlex 700H
and 700S Drives Installation Manual,
publication PFLEX-IN006, for information
on installing this option board.

60

Hrdwr Therm

3

1 The thermistor input is activated

(>4 k

Ω

) on the 20C-DG1 option

board.

1. Check the motor.
2. The resistance of the thermistor input

must go below 2 k

Ω

before the drive can

be reset.

63

Shear Pin

3

The value programmed in
parameter 148 [Current Lmt Val]
has been exceeded. You can
enable/disable this fault with
parameter 238 [Fault Config 1]
(

page 42

).

Check the load requirements and the value
in [Current Lmt Val].

65

I/O Removed

2

An I/O option board has been
removed.

Clear the fault.

No. Name

Fa

u

lt

Alarm

Description

Action (if applicable)