Troubleshooting

Chapter 3

Stopping the Drive Results in a Decel Inhibit Fault

Technical Support Options

Technical Support Wizards

If you are connected to a drive via DriveExplorer™ or DriveExecutive™, you can
run a Tech Support wizard to gather information that will help diagnose
problems with your drive and/or peripheral device. The information gathered by
the wizard is saved as a text file and can be emailed to your remote technical
support contact. (See

What You Need When You Call Tech Support on page 80

for more information.)

To run a Tech Support wizard in DriveExplorer, select Wizards from the Actions
menu. In DriveExecutive, select Wizards from the Tools menu. Or, click the

button. Follow the prompts to complete the wizard.

Cause(s)

Indication

Corrective Action

The bus regulation feature is enabled and
is halting deceleration due to excessive
bus voltage. Excess bus voltage is
normally due to excessive regenerated
energy or unstable AC line input voltages.
Internal timer has halted drive operation.

Decel Inhibit fault
screen.
LCD Status Line
indicates “Faulted”.

1. See Attention statement on page

page 8

.

2. Reprogram parameters 161/162 to eliminate any

“Adjust Freq” selection.

3. Disable bus regulation (parameters 161 & 162) and

add a dynamic brake.

4. Correct AC input line instability or add an isolation

transformer.

5. Reset drive.