Chapter 3

106 MCB-PB Config

2

The drive rating information stored
on the power board is incompatible
with the Main Control board.
See

Table 27, “Main Control Board -

Power Board Configuration Fault
(F106) Subcode,” on page 76

for

more information on this fault.

1. Reset the fault or cycle the power.
2. Replace the Main Control board.

107 New IO Option

2

A New option board was added to
the Main Control board.
See

Table 21, “Device Change (F44),

Device Added (F45), I/O Option
Board Removed (F65), Power Board
Checksum (F104), New I/O Option
Board (F107) and I/O Option Board
Change (F120) Fault Subcodes,” on
page 75

for more information on

this fault.

1. Restore the drive to the factory defaults.
2. Reprogram parameters as necessary.

113 Fatal App

2

A Fatal Application error has
occurred.

Replace the Main Control board.

114 AutoT Enable

2

Autotune is enabled but has not
started.

Press the Start key within 20 seconds of
enabling autotune.

120 I/O Change

2

An option board has been replaced.
See

Table 21, “Device Change (F44),

Device Added (F45), I/O Option
Board Removed (F65), Power Board
Checksum (F104), New I/O Option
Board (F107) and I/O Option Board
Change (F120) Fault Subcodes,” on
page 75

for more information on

this fault.

Reset the fault.

121 I/O Comm Loss

2

An I/O Board lost communications
with the Main Control board.

1. Check the connector.
2. Check for induced noise.
3. Replace I/O board or Main Control board.

133 DigIn CnflctA

2 Digital input functions are in conflict. Combinations marked with a “ ” will cause

an alarm.

134 DigIn CnflctB

2 A digital Start input has been configured without a Stop input or other functions

are in conflict. Combinations that conflict are marked with a “ ” and will cause
an alarm.

No. Name

Fa

u

lt

Alarm

Description

Action (if applicable)

* Jog 1 and Jog 2

Acc2/
Dec2

Accel 2 Decel 2 Jog* Jog Fwd Jog Rev Fwd/Rev

Acc2 / Dec2
Accel 2
Decel 2
Jog*
Jog Fwd
Jog Rev
Fwd/Rev

* Jog 1 and Jog 2

Start Stop-

CF

Run Run

Fwd

Run
Rev

Jog* Jog

Fwd

Jog Rev Fwd/

Rev

Start
Stop-CF
Run
Run Fwd
Run Rev
Jog*
Jog Fwd
Jog Rev
Fwd/Rev