Chapter 2

Programming and Parameters

Speed Command File

Fil

e

Gr

ou

p

No

.

Parameter Name & Description

Values

Rela

ted

SPEED C

O

MMAND

Spd Mode/Limits

079 [Speed Units]

Selects the units to be used for all speed related
parameters. Options 0 & 1 indicate status only.
Options 2 & 3 will convert/configure the drive for
that selection.
“Convert Hz” (2) - converts all speed based
parameters to Hz, and changes the value
proportionately (i.e. 1800 RPM = 60 Hz).
“Convert RPM” (3) - converts all speed based
parameters to RPM, and changes the value
proportionately.
Note: This parameter does not get changed with a
“Reset to Defaults”.

Default:

Options:

0

0
1
2
3

“Hz”

“Hz”
“RPM”
“Convert Hz”
“Convert RPM”

080 [Feedback Select]

Selects the source for motor speed feedback.
“Open Loop” (0) - no encoder is present, and slip
compensation is not needed.
“Slip Comp” (1) - tight speed control is needed,
and encoder is not present.

Default:

Options:

0

0
1

“Open Loop”

“Open Loop”
“Slip Comp”

152

081 [Minimum Speed]

Sets the low limit for speed reference after scaling
is applied. Refer to parameter 083 [Overspeed
Limit].

Default:

Min/Max:
Units:

0.0

0.0/[Maximum Speed]
0.1 Hz
0.1 RPM

079
083
092
095

082 [Maximum Speed]

Sets the high limit for speed reference after
scaling is applied. Refer to parameter 083
[Overspeed Limit].

Default:

Min/Max:

Units:

50.0 or 60.0 Hz (volt class)
[Motor NP RPM]

5.0/320.0 Hz
75.0/19200.0 RPM
0.1 Hz
0.1 RPM

055
079
083
091
094

083 [Overspeed Limit]

Sets the incremental amount of the output
frequency (above [Maximum Speed]) allowable
for functions such as slip compensation.
[Maximum Speed] + [Overspeed Limit] must be

[Maximum Freq]

Default:

Min/Max:

Units:

10.0 Hz
300.0 RPM

0.0/20.0 Hz
0.0/600.0 RPM
0.1 Hz
0.1 RPM

055
079
082

084
085
086

[Skip Frequency 1]
[Skip Frequency 2]
[Skip Frequency 3]

Sets a frequency at which the drive will not
operate. [Skip Frequency x] and [Skip Frequency
Band] must not equal 0.

Default:
Default:
Default:

Min/Max:
Units:

Based on Drive Rating
0.0 Hz
0.0 Hz

–/+[Maximum Speed]
0.1 Hz

087

087 [Skip Freq Band]

Determines the bandwidth around a skip
frequency. [Skip Freq Band] is split, applying 1/2
above and 1/2 below the actual skip frequency.
The same bandwidth applies to all skip
frequencies.

Default:

Min/Max:
Units:

0.0 Hz

0.0/30.0 Hz
0.1 Hz

084
085
086

32

32

32

Allowable Output Frequency Range

Bus Regulation or Current Limit

V

olta

g

e

Frequency

Allowable Output Frequency Range

Normal Operation

Allowable Reference Frequency Range

Frequency Trim due to
Speed Control Mode

Motor Volts

Break Volts

Start Boost

0

Min

Speed

Motor

Hz

Max

Speed

Output

Freq Limit

Max
Freq

Break

Frequency

Overspeed

Limit

32