Rockwell Automation 20C PowerFlex 700H Drives Programming User Manual

Page 22

Advertising
background image

22

Rockwell Automation Publication 20C-PM001F-EN-P - March 2012

Chapter 2

Programming and Parameters

MO

TO

R

C

O

NT

ROL

M

otor D

at

a

046 [Mtr NP Pwr Units]

Selects the motor power units to be used.
“Convert HP” = converts all power units to
Horsepower.
“Convert kW” = converts all power units to
kilowatts.
Note: This parameter does not get changed with a
“Reset to Defaults”.

Default:

Options:

0
1
2
3

Based on Drive Rating

“Horsepower”
“kiloWatts”
“Convert HP”
“Convert kW”

047 [Motor OL Hertz]

Selects the output frequency below which the
motor operating current is derated. The motor
thermal overload will generate a fault at lower
levels of current below this output frequency.

Default:

Min/Max:
Units:

Motor NP Hz/3

0.0/Motor NP Hz
0.1 Hz

042
220

048 [Motor OL Factor]

Sets the operating level for the motor overload.

Default:

Min/Max:
Units:

1.00

0.20/2.00
0.01

042
220

049 [Motor Poles]

Defines the number of poles in the motor.
Note: Maximum value changed from 12 to 18 for
firmware revision 4.001.

Default:

Min/Max:
Units:

4

2/18
1 Pole

050 [Motor OL Mode]

“Pwr Cyc Ret” - If “0”, the value of parameter 220 [Motor OL Count] is reset to zero by a drive reset
or power cycle. If “1”, the value of parameter 220 [Motor OL Count] is maintained. A “1” to “0”
transition resets parameter 220 [Motor OL Count] to zero.
Note: Added for firmware revision 3.001.
1 = Enabled
0 = Disabled

220

To

rq

A

tt

ribu

tes

053 [Motor Cntl Sel]

Sets the method of motor control used in the
drive.

Default:

Options:

0

0
1
2
3

“Sensrls Vect”

“Sensrls Vect”
“SV Economize”
“Custom V/Hz”
“Fan/Pmp V/Hz”

055 [Maximum Freq]

Sets the highest frequency the drive will output.
Refer to parameter 083 [Overspeed Limit].

Default:

Min/Max:
Units:

Based on Drive Rating

5.0/320.0 Hz
0.1 Hz

083

056 [Compensation]

“Mtr Lead Rev” - If “1”, reverses the phase rotation of the applied voltage, effectively reversing
the motor leads.
Notes: Not retained when the parameters are reset to defaults. Added for firmware revision
3.001.
1 = Enabled
0 = Disabled

Fil

e

Gr

oup

No

.

Parameter Name & Description

Values

Rela

ted

Motor

FLA

OL

Factor

Operating

Level

=

x

Name

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Pw

r C

yc

R

et

Default

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

0

Bit

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Name

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Mt

r L

ead R

ev

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Default

x

x

x

x

x

x

x

x

x

x

0

x

x

x

x

x

Bit

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Advertising