[Motor OL Hertz]. For all settings of [Motor OL Hertz] other than zero, the
overload capacity is reduced to 70% at an output frequency of zero.

[Motor NP FLA] is multiplied by [Motor OL Factor] to select the rated current
for the motor thermal overload. This can be used to raise or lower the level of
current that will cause the motor thermal overload to trip. The effective overload
factor is a combination of [Motor OL Hertz] and [Motor OL Factor].

Changing Overload Hz

0

10

20

30

40

50

60

70

80

90 100

% of Base Speed

Contin

uous Rating

OL Hz = 10
OL Hz = 25
OL Hz = 50

0

20

40

60

80

100

120

Changing Overload Factor

0

10

20

30

40

50

60

70

80

90 100

% of Base Speed

Contin

uous Rating

OL % = 1.20
OL % = 1.00
OL % = 0.80

0

20

40

60

80

100

120

140

Note: This graph represents a motor with a speed range of 2:1.