Troubleshooting

Publication 1771-UM002A–EN–P – May 2000

Table 5.A
Power-Up Troubleshooting

Led Indication

Possible Cause

Corrective Action

PC COMM FAULT

1

EXPANDER COMM FAULT

1

ACTIVE

1

MODULE FAULT

2

Normal Operation

None

PC COMM FAULT
EXPANDER COMM FAULT
ACTIVE
MODULE FAULT

Expander address is incorrect.
More than one 1771-M1 module in the
chassis
No 1771-OJ module in the chassis

Switch 3 on 1771-OJ module must be 001,
010 or 011.
Install only one 1771-M1 module per chassis.
Install at least one 1771-OJ module per
chassis.

PC COMM FAULT
EXPANDER COMM FAULT
ACTIVE
MODULE FAULT

Block transfer error

Check cables and adapters for faulty or
intermittent operation.
Check for invalid block transfer starting
address.

PC COMM FAULT
EXPANDER COMM FAULT
ACTIVE
MODULE FAULT

Communications error between 1771-M1
module and 1771-OJ

Check that all modules are properly installed
in chassis.
Noisy environment: check earth grounding of
chassis power supplies, stepper
motor/translator and noise sources (relays,
motors, etc.) too close to the chassis.

PC COMM FAULT
EXPANDER COMM FAULT
ACTIVE
MODULE FAULT

Hardware failure

Cycle power to chassis.
If problem still exists, replace module.

PC COMM FAULT
EXPANDER COMM FAULT
ACTIVE
MODULE FAULT

Communications error between 1771-M1 and
1771-OJ modules
Initialization error
Watchdog timers timed-out

See CORRECTIVE ACTION above for
Comm. Error between 1771-M1 and 1771-OJ
modules.
Hardware error, see above
Hardware error, see above

1

LED indicators on the stepper controller module

2

LED indicator on the pulse output expander module

Legend: ON OFF Flashing