The following three examples show how this equation can be used.

Example Problem 1: Single-step mode or independent mode.

For the next move of a move profile, the change in move position
from beginning to end (DELPOS) must be 26k pulses. Determine
the maximum allowable final rate (FR) when using equal ramp and
decel times of 4 seconds.

The parameters of the equation (IR, FR, RT and DELPOS) and a
sketch of the move are shown in Figure 3.20.

Figure 3.20
Single Step or Independent Mode

Rate

FR

IR

RT

DT

DEL POS

Start
Position

Final
Position

10530

Position

20 ms

Solution

Write down the known facts.

1. RT = DT = 4 seconds

DELPOS = 26k pulses
IR = 0 (The initial rate of a move in the single step or
independent mode is zero by definition.)

Find FR, the maximum final rate.

4(FR + 0)

+ FR

+ 0.02 < 26k

2

2

4

Choose a value for FR, say 10k pulses per second.