Rockwell Automation 1771-QA Stepper Positioning Assembly User Manual User Manual

Page 41

Advertising
background image

3–19

Programming and Operation

Publication 1771-UM002A–EN–P – May 2000

Move Data

Move data is contained in the remaining five words of the move
block (Figure 3.13). Values are entered in BCD. Those shown in
Figure 3.13 are the maximum allowable values. Undefined bits (bits
14-17) in the words specifying the ramp, decel and position must be
filled with zeros.

Figure 3.13
Move Block

17

10 07

00

Data Table

9

9

9

9

9

9

9

9

9

9

0

0

0

0

10525

9

9

9

0

0

0

0

9

9

9

0

0

0

0

0

0

0

0

Single Move Control Word

0 – 9.99 Seconds

0 – 9,999 x 1
0 – 2,000 x 10

0 – 9.99 seconds

0 – 999,999 Pulses

SMCW

Ramp

Rate

Decel

MS Position

LS Position

Pulses per
second

Ramp Time

The ramp value is the number of seconds the positioning assembly
will take to reach a (new) final rate. In the continuous mode, the
final rate can be greater than or less than the starting rate. Ramp
time can be any value between 0 and 9.99 seconds. Refer to section
titled “Application Considerations.”

Final Rate

The final rate value determines the constant speed of the move. The
rate can be any value between 0 and 9,999 pulses per second or in
increments of 10 pulses per second between 0 and 20,000 pulses per
second. Refer to section titled “Application Considerations.”

Important:

When the rate multiplier bit (bit 01) of the single move
control word is set, the resulting rate will be equal to the
programmed rate value times ten.

Decel

The deceleration value is the number of seconds the positioning
assembly will take to decelerate to zero pulses per second. It should
not be confused with a ramp to a lower final rate other than zero.
The decel is an active part of the move profile in the single step and
independent modes.

Advertising