Rockwell Automation 1771-QA Stepper Positioning Assembly User Manual User Manual

Page 70

Advertising
background image

3–48

Programming and Operation

Publication 1771-UM002A–EN–P – May 2000

The parameters of the equation (IR, FR, RT and DELPOS) and a
sketch of the move are shown in Figure 3.22.

Figure 3.22
Last Move in a Continuous Mode

IR

Rate

FR

RT

DT

DEL POS

Position

Final

Position

Start

Position

10531

20 ms

Solution: Write down the known facts.

RT = 6 seconds
IR = 12k pulses per second (final rate of previous move)
FR = 6k pulses per second
DELPOS = 62k pulses (742k pulses - 680k pulses)

6(6k + 12k)

+ 6k

+ 0.02 < 62k

2

2

DT

+ 6k

+ 0.02 < 62k

2

DT

54k

6k

+ 0.02 < 8k

2

DT

+ 0.02 < 1.33

2

DT

< 1.31

2

DT

Therefore, a decel time of 2 seconds is acceptable for the move.

Reversing Direction During a Continuous Sequence

In order to reverse direction during a positioning sequence in the
continuous mode, a move to 0Hz rate must be achieved. The
procedure for achieving a 0Hz rate as stated in the paragraph titled
“Decel and Position Considerations for a 0Hz Rate Move” should be
followed.