Rockwell Automation 1771-QA Stepper Positioning Assembly User Manual User Manual

Page 64

Advertising
background image

3–42

Programming and Operation

Publication 1771-UM002A–EN–P – May 2000

Processor Scan Time PS = (5ms/lK words) x (4K words) =
20ms.
Processor I/O Scan Time PIO = (0.5ms/rack number x (4
rack numbers) = 2ms
Number of Words Transferred = 64 (write) or 10 (read)

3. Calculate the block transfer times T for the write and read

operation.

T = 0.1 + (.075ms/word x 64 words)
= 0.1 + 4.8
= 4.9ms (write)

T = 0.1 + (.075ms/word x 10 words)
= 0.1 + .75
= .85ms (read)

4. Calculate the worst case system time ST between 2 consecutive

write block transfers.

The stepper controller module toggles to a read operation in the scan
following completion of the write operation.

ST = PS + PIO + T(1) + T(2) + T(3) + T(4) (writes)
PS + PIO + T(1) + T(2) + T(3) + T(4) (reads)

ST = 2PS + 2PIO + 4T (write) + 4T (read)
= 2(20) + 2(2) + 4(4.9) + 4(.85)
= 40 + 4 + 19.6 + 369
= 67 ms

This is the worst case time between two consecutive write block
transfers in the 4-chassis local configuration described in example
problem 2 (enabled stepper assembly in each chassis).

Mini-PLC-2/15 Controller

The program scan and I/O scan are consecutive and are considered as
a single processor scan. The Mini-PLC-2/15 scan time varies
typically from 18 to 24ms for a 1K program and one I/O rack. Each
block transfer module will be updated during a program scan.

The procedure for calculating the worst case time between transfers
can be done in three steps.

1. Write down the known facts and system values.

Processor Scan time PS = 24ms

Number of Words Transferred W default value of the module

2. Calculate the block transfer time T for the read and write

operation.

Advertising