3–50

Programming and Operation

Publication 1771-UM002A–EN–P – May 2000

The parameters of the equation (DELPOS, T and IR) and a sketch of
the move are shown in Figure 3.23.

Figure 3.23
0Hz Rate Move

Rate

IR

T

DEL POS

Start
Position

Final

Position

Position

10533

20 ms

Example Problem 1:

The seventh move of a profile in continuous mode must be brought
to 0Hz rate so that the profile can return to its starting point value.
The final rate and final position of the previous move are 16k pulses
per second and 510k pulses, respectively. The seventh move must
reach a 0Hz rate at 620k pulses. What decel time should be
programmed? How can this move be achieved?

Solution: Write down the known facts.

IR = 16k (final rate of previous move)
DELPOS = 110k (620k - 510k pulses)

T

2 DELPOS

IR

– 0.04

(Line 1)

T

2(110k)

IR

– 0.04

(Line 2)

T

220k

IR

– 0.04

(Line 3)

T = 13.75 seconds