Rockwell Automation 1771-QA Stepper Positioning Assembly User Manual User Manual

Page 63

Advertising
background image

3–41

Programming and Operation

Publication 1771-UM002A–EN–P – May 2000

3. Calculate the block transfer time T for the read and write

operation.

T = 0.1ms + (.075ms/word x number of words transferred)

The same equation is used for either read or write transfer times.

4. Calculate the worst case system time ST between transfers.

ST = PS + PIO + T(1) + T(2) + T(3) +...

Example Problem 2

A PLC-2/30 programmable controller is controlling four I/O racks in
a local configuration (Figure 3.19). Otherwise this example problem
is identical to example problem 1.

Figure 3.19
Local System Example

1771–AL

1771–QA

Rack No. 1

1771–AL

1771–QA

Rack No. 2

1771–AL

1771–QA

Rack No. 3

1771–AL

1771–QA

Rack No. 4

10536

PLC–2/30

Solution

1. Write down the known facts.

Program length = 4K words
Number of chassis = 4 rack numbers
Number of default block transfer words = 64 words (write),
10 words (read)

2. Calculate the system values.

Advertising