2–7

Assembly and Installation

Publication 1771-UM002A–EN–P – May 2000

Table 2.D
Expander Module Address (S3)

Switch Assembly S3

Expander

Switch 1

Switch 2

Switch 3

Address

ON

OFF

OFF

1

OFF

ON

OFF

2

ON

ON

OFF

3

Expander Module Output (S4, S5, S6)

The choice of pulse output expander module output, either push-pull,
current source (open emitter) or current sink (open collector), is
user-selectable to best match the input characteristics of the stepper
translator.

PUSH-PULL-OPEN The push-pull output is compatible with many
stepper translators. The expander module output is wired to the
translator input as shown in Figure 2.1.

CURRENT SOURCE or CURRENT SINK-OPEN When using the
expander module as a current source or sink for the output pulses, it
may be necessary to use a pull-down or pull-up resistor, respectively
(Figure 2.3) Refer to the translator input specifications and
installation instructions for correct use of this resistor if it is required.

Figure 2.3
Output Source or Sink Connections

Common

Direction

+Supply
Pull–Up

–Supply

Translator

Expander Module

12

11

10

3

10512

Resistors
(Current Sink)

or

Pull–Down
Resistors
(Current Source)

The positive (+) and negative (-) terminals of the output power
supply must be connected to the + DC OUTPUT SUPPLY and
COMMON terminals, respectively, of the module field wiring arm
regardless of the choice of module output.