Communicate with Devices on a DeviceNet Network

Appendix A

9. Click the Scanlist tab to upload the configuration from the device to the

software configuration.

The Scanner Configuration Applet dialog box appears.

10. Click Upload.

The Scanlist 1784-PCIDS DeviceNet Scanner dialog box appears.

11. Click Add All to add all of the available devices to the Scanlist.

ADR

On the ADR property tab, you can configure the automatic device replacement (ADR) parameters for scanners that support the ADR feature, which automates the
replacement of a failed slave device on a DeviceNet network by returning it to the prior level of operation. This feature includes Configuration Recovery (CR) and
Auto-address Recovery (AAR). By using the controls on this tab, you can choose ADR parameters and enable/disable this functionality either globally or on a device-
specific basis.

Summary

Shows a summary of the configuration. This screen is read-only.

Table 9 - General Device Properties Tab Descriptions

Tab

Definition