Appendix F

Status Indicators

Network Status (NET) Indicator

Module Status (OK) Indicator

NET Indicator

Display

Description

Solid green

CIP connections
established

The module has an IP address and CIP connections (Class 1 or

Class 3) are established.

Normal operation. No action required.

Flashing green

No CIP connections
established

The module has an IP address, but no CIP connections are

established.

Normal operation if no connections are configured. No action

required.

If connections are configured, check connection originator for

connection error code.

Flashing red

Lost network
connection

The module detected that the network connection has been

lost.

Verify that all Ethernet cables are connected.
Verify that the Ethernet switch is powered.

OK Indicator

Display

Description

Solid green

OK

The module is operating correctly.
Normal operation. No action required.

Flashing green

Standby

The module is not configured correctly.
Verify the module’s configuration.

Solid red

Major fault

An unrecoverable fault has occurred.
Cycle power to the controller. Correct the fault.

Flashing red

Minor fault

A recoverable fault has occurred. Correct the fault.