Rockwell Automation Publication 1789-UM002J-EN-P - December 2012

213

Communicate with Devices on a ControlNet Network

Appendix B

7. On the Network Parameters tab, specify the network update time (NUT).

The default NUT is 5 ms. The NUT you specify must be lower than or
equal to the lowest RPI in your system.

8. Enter the Pending Max Scheduled Address and Pending Max

Unscheduled Address.

9. Click Apply to save the information you entered.

10. Click the Media Configuration tab.

The Media Configuration tab appears.

11. Enter data on the media tab to match your system.
12. Click OK.